schneider LC1F5004FD

Selling Points

  • 1High Performance: Designed for reliable operation in industrial environments.
  • 24-Pole Configuration: Suitable for a variety of applications requiring multiple control circuits.
  • 3110V DC Coil: Compatible with DC power systems, ensuring efficient control.
  • 44NO Contacts: Ensures consistent and reliable switching performance.
  • 5Durable Construction: Built with high-quality materials to withstand harsh industrial conditions.
Product Details
LC1F5004FD
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /><= 460 V DC
[Uc] control circuit voltage
110 V DC
[Ie] rated operational current
700 A (at <104 °F (40 °C)) at <= 440 V AC AC-1
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
700 A (at 104 °F (40 °C))
Rated breaking capacity
4000 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
4200 A 104 °F (40 °C) - 10 s<br />3200 A 104 °F (40 °C) - 30 s<br />2400 A 104 °F (40 °C) - 1 min<br />1500 A 104 °F (40 °C) - 3 min<br />1200 A 104 °F (40 °C) - 10 min
Associated fuse rating
500 A aM at <= 440 V<br />800 A gG at <= 440 V
Average impedance
0.18 mOhm - Ith 700 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
88 W AC-1
Overvoltage category
III
power pole contact composition
4 NO
Control circuit voltage limits
Operational 0.85...1.1 Uc 131 °F (55 °C))<br />Drop-out 0.2...0.35 Uc 131 °F (55 °C))
Mechanical durability
10 Mcycles
Inrush power in W
1100 W 68 °F (20 °C))
Hold-in power consumption in W
6 W 68 °F (20 °C)
Maximum operating rate
2400 cyc/h 131 °F (55 °C)
Operating time
50...60 ms closing<br />45...60 ms opening
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 40 x 5 mm<br />Power circuit lugs-ring terminals 2 0.4 in² (240 mm²)<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 309.8 lbf.in (35 N.m)
Mounting Support
Plate
Heat dissipation
6 W
Standards
EN 60947-4-1<br />IEC 60947-4-1<br />JIS C8201-4-1<br />IEC 60947-1<br />EN 60947-1
Product Certifications
CB<br />RINA<br />BV<br />ABS<br />LROS (Lloyds register of shipping)<br />RMRoS<br />CCC<br />DNV<br />UL<br />UKCA
compatibility code
LC1F
Control circuit type
DC standard
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Height
9.4 in (238 mm)
Width
11.3 in (288 mm)
Depth
9.1 in (232 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
28.55 lb(US) (12.95 kg)