Product Model
LC1F630

Selling Points
- 1High durability: 1200 cycles/hour for operating rate.
- 2High reliability: Environments tolerance up to 55°C.
- 3Suitable for motor applications up to 250kW@400V.
- 4No coil to allow later selection and installation.
- 5Made with recycled cardboard packaging for sustainability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range | TeSys | Product name | TeSys F |
Product or Component Type | Contactor | Device short name | LC1F |
Contactor application | Resistive load<br />Motor control | Utilisation category | AC-4<br />AC-1<br />AC-3 |
Poles description | 3P | power pole contact composition | 3 NO |
[Ue] rated operational voltage | <= 1000 V AC 50/60 Hz<br /> <= 460 V DC | [Ie] rated operational current | 1000 A 104 °F (40 °C)) <= 440 V AC AC-1<br />630 A 131 °F (55 °C)) <= 440 V AC AC-3 |
Motor power kW | 335 kW at 380...400 V AC 50/60 Hz (AC-3)<br />375 kW at 415 V AC 50/60 Hz (AC-3)<br />400 kW at 440 V AC 50/60 Hz (AC-3)<br />400 kW at 500 V AC 50/60 Hz (AC-3)<br />450 kW at 1000 V AC 50/60 Hz (AC-3)<br />200 kW at 220...240 V AC 50/60 Hz (AC-3)<br />450 kW at 660...690 V AC 50/60 Hz (AC-3)<br />100 kW at 400 V AC 50/60 Hz (AC-4) | [Uc] control circuit voltage | 48...1000 V AC 40...400 Hz with LX1/LX9 coil<br />48...440 V DC with LX4 coil |
[Uimp] rated impulse withstand voltage | 8 kV | Overvoltage category | III |
[Ith] conventional free air thermal current | 1000 A (at 104 °F (40 °C))<br />1250 A | Irms rated making capacity | 6300 A AC conforming to IEC 60947-4-1 |
Rated breaking capacity | 5040 A conforming to IEC 60947-4-1 | [Icw] rated short-time withstand current | 5050 A 104 °F (40 °C) - 10 s<br />4400 A 104 °F (40 °C) - 30 s<br />3400 A 104 °F (40 °C) - 1 min<br />2200 A 104 °F (40 °C) - 3 min<br />1600 A 104 °F (40 °C) - 10 min |
Associated fuse rating | 630 A aM at <= 440 V<br />1000 A gG at <= 440 V | Average impedance | 0.12 mOhm - Ith 1000 A 50 Hz |
[Ui] rated insulation voltage | 1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C | Power dissipation per pole | 120 W AC-1<br />48 W AC-3 |
Control circuit voltage limits | Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil<br />Drop-out: 0.25...0.5 Uc AC 40...400 Hz with LX1/LX9 coil<br />Operational: 0.85...1.1 Uc DC with LX4 coil<br />Drop-out: 0.2...0.35 Uc DC with LX4 coil | Heat dissipation | 20 W |
Operating time | 40...80 ms closing with LX1/LX9 coil<br />100...200 ms opening with LX1/LX9 coil<br />60...70 ms closing with LX4 coil<br />40...50 ms opening with LX4 coil | Mounting Support | Plate |
Standards | EN 60947-4-1<br />IEC 60947-4-1<br />IEC 60947-1<br />JIS C8201-4-1<br />EN 60947-1 | Product Certifications | ABS<br />UL<br />RINA<br />DNV<br />CSA<br />CB<br />LROS (Lloyds register of shipping)<br />BV<br />RMRoS<br />UKCA |
Connections - terminals | Power circuit bar 2 60 x 5 mm<br />Power circuit bolted connection<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²) | Tightening torque | Power circuit 513.3 lbf.in (58 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m) |
Mechanical durability | 5 Mcycles | Inrush power in VA | 1500…1730 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />1420…1920 VA (at 68 °F (20 °C))with LX4 coil |
Hold-in power consumption in VA | 20…25 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />6.5…12.5 VA (at 68 °F (20 °C))with LX4 coil | Maximum operating rate | 1200 cyc/h 131 °F (55 °C) |
Compatibility code | LC1F | IP degree of protection | IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106 |
Protective treatment | TH | Ambient Air Temperature for Operation | 23…131 °F (-5…55 °C) |
Ambient Air Temperature for Storage | -76…176 °F (-60…80 °C) | Permissible ambient air temperature around the device | -40…158 °F (-40…70 °C) |
Operating altitude | 9842.52 ft (3000 m) without derating | Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed4 Gn, 5...300 Hz<br />Shocks contactor open6 Gn for 1/2 sine wave (11 ms)<br />Shocks contactor closed15 Gn for 1/2 sine wave (11 ms) |
Height | 12.0 in (304 mm) | Width | 12.2 in (309 mm) |
Depth | 10.04 in (255 mm) | Net Weight | 41.006 lb(US) (18.6 kg) |
Specifications may be subject to change without notice