schneider LC1F6304

Selling Points

  • 1Controls motors up to 1000A (500 kW / 440 V) for high-power applications.
  • 2Compatible with LX1/LX9 coil for 1000 Vac 40/400Hz and LX4 coil for 48-440 Vdc.
  • 3Features 4 poles (4 NO) for reliable contact operation.
  • 4Designed for resistive load applications with high reliability and durability.
  • 5Easy installation and maintenance with a drawer for coil insertion and add-on blocks.
Product Details
LC1F6304
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Product name
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
power pole contact composition
4 NO
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
1000 A 104 °F (40 °C)) <= 440 V AC AC-1
[Uc] control circuit voltage
48...1000 V AC 40...400 Hz with LX1/LX9 coil<br />48...440 V DC with LX4 coil
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
1000 A (at 104 °F (40 °C))<br />1250 A
Irms rated making capacity
6300 A AC conforming to IEC 60947-4-1
Rated breaking capacity
5040 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
5050 A 104 °F (40 °C) - 10 s<br />4400 A 104 °F (40 °C) - 30 s<br />3400 A 104 °F (40 °C) - 1 min<br />2200 A 104 °F (40 °C) - 3 min<br />1600 A 104 °F (40 °C) - 10 min
Associated fuse rating
630 A aM at <= 440 V<br />1000 A gG at <= 440 V
Average impedance
0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
120 W AC-1
Control circuit voltage limits
Operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil<br />Drop-out: 0.25...0.5 Uc AC 40...400 Hz with LX1/LX9 coil<br />Operational: 0.85...1.1 Uc DC with LX4 coil<br />Drop-out: 0.2...0.35 Uc DC with LX4 coil
Heat dissipation
20 W
Operating time
40...80 ms closing with LX1/LX9 coil<br />100...200 ms opening with LX1/LX9 coil<br />60...70 ms closing with LX4 coil<br />40...50 ms opening with LX4 coil
Mounting Support
Plate
Standards
EN 60947-4-1<br />IEC 60947-4-1<br />IEC 60947-1<br />JIS C8201-4-1<br />EN 60947-1
Product Certifications
ABS<br />UL<br />RINA<br />DNV<br />CSA<br />CB<br />LROS (Lloyds register of shipping)<br />BV<br />RMRoS<br />UKCA
Connections - terminals
Power circuit bar 2 60 x 5 mm<br />Power circuit bolted connection<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)solid without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)
Tightening torque
Power circuit 513.3 lbf.in (58 N.m)<br />Control circuit 10.6 lbf.in (1.2 N.m)
Mechanical durability
5 Mcycles
Inrush power in VA
1500…1730 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />1420…1920 VA (at 68 °F (20 °C))with LX4 coil
Hold-in power consumption in VA
20…25 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil<br />6.5…12.5 VA (at 68 °F (20 °C))with LX4 coil
Maximum operating rate
1200 cyc/h 131 °F (55 °C)
compatibility code
LC1F
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C)
Operating altitude
9842.52 ft (3000 m) without derating
Mechanical robustness
Vibrations contactor open2 Gn, 5...300 Hz<br />Vibrations contactor closed4 Gn, 5...300 Hz<br />Shocks contactor open6 Gn for 1/2 sine wave (11 ms)<br />Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Height
12.0 in (304 mm)
Width
15.3 in (389 mm)
Depth
10.04 in (255 mm)
Net Weight
47.4 lb(US) (21.5 kg)

Specifications may be subject to change without notice