schneider LC1F800QW

Selling Points

  • 1High-performance motor control for AC-3 applications.
  • 2800A rated operational current at 440V AC.
  • 3Compatible with 380-440V AC and 400V DC control circuits.
  • 4Robust construction with 5 million mechanical cycles.
  • 5Fast operating time of 40-50 ms for opening and 60-80 ms for closing.
Product Details
LC1F800QW
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys F
Product or Component Type
Contactor
Device short name
LC1F
Contactor application
Resistive load<br />Motor control
Utilisation category
AC-3<br />AC-1<br />AC-4
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /><= 460 V DC
[Uc] control circuit voltage
400 V DC<br />380...415 V AC 40...400 Hz
[Ie] rated operational current
1000 A (at <104 °F (40 °C)) at <= 440 V AC AC-1<br />800 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
1000 A (at 104 °F (40 °C))
Rated breaking capacity
6400 A conforming to IEC 60947-4-1
[Icw] rated short-time withstand current
5500 A 104 °F (40 °C) - 10 s<br />4600 A 104 °F (40 °C) - 30 s<br />3600 A 104 °F (40 °C) - 1 min<br />2600 A 104 °F (40 °C) - 3 min<br />1700 A 104 °F (40 °C) - 10 min
Associated fuse rating
1000 A gG at <= 440 V<br />800 A aM at <= 440 V
Average impedance
0.12 mOhm - Ith 1000 A 50 Hz
[Ui] rated insulation voltage
1000 V IEC 60947-4-1<br /> 1500 V VDE 0110 group C
Power dissipation per pole
120 W AC-1<br />77 W AC-3
Overvoltage category
III
power pole contact composition
3 NO
Motor power kW
450 kW at 1000 V AC 50/60 Hz (AC-3)<br />450 kW at 500 V AC 50/60 Hz (AC-3)<br />475 kW at 660...690 V AC 50/60 Hz (AC-3)<br />110 kW at 400 V AC 50/60 Hz (AC-4)<br />450 kW at 380...400 V AC 50/60 Hz (AC-3)<br />450 kW at 415 V AC 50/60 Hz (AC-3)<br />450 kW at 440 V AC 50/60 Hz (AC-3)<br />250 kW at 220...230 V AC 50/60 Hz (AC-3)
Control circuit voltage limits
Operational 0.85...1.1 Uc 131 °F (55 °C))<br />Drop-out 0.3...0.5 Uc 131 °F (55 °C))
Mechanical durability
5 Mcycles
Inrush power in W
1900 W 68 °F (20 °C))
Hold-in power consumption in W
12 W 68 °F (20 °C)
Maximum operating rate
600 cyc/h 131 °F (55 °C)
Operating time
40...50 ms opening<br />60...80 ms closing
Connections - terminals
Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)flexible without cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)flexible with cable end<br />Control circuit screw clamp terminals 2 0.002…0.004 in² (1…2.5 mm²)flexible with cable end<br />Control circuit screw clamp terminals 1 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Control circuit screw clamp terminals 2 0.002…0.006 in² (1…4 mm²)solid without cable end<br />Power circuit bar 2 60 x 5 mm<br />Power circuit bolted connection
Tightening torque
Control circuit 10.6 lbf.in (1.2 N.m)<br />Power circuit 513.3 lbf.in (58 N.m)
Mounting Support
Plate
Heat dissipation
12 W
motor power range
250…500 kW 200…240 V 3 phase<br />250…500 kW 380…440 V 3 phase<br />110…220 kW 200…240 V 3 phase<br />250…500 kW 480…500 V 3 phase
Motor starter type
Direct on-line contactor
Contactor coil voltage
400 V DC standard<br />400 V AC standard<br />380 V AC standard<br />415 V AC standard
Standards
JIS C8201-4-1<br />IEC 60947-4-1<br />EN 60947-4-1<br />IEC 60947-1<br />EN 60947-1
Product Certifications
UL<br />CSA<br />RMRoS<br />CB<br />ABS<br />CCC<br />UKCA
compatibility code
LC1F
Control circuit type
DC standard<br />AC 40...400 Hz
IP degree of protection
IP20 front face with shrouds IEC 60529<br />IP20 front face with shrouds VDE 0106
Protective treatment
TH
Ambient Air Temperature for Operation
23…131 °F (-5…55 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Permissible ambient air temperature around the device
23…131 °F (-5…55 °C)
Height
12.0 in (304 mm)
Width
12.2 in (309 mm)
Depth
10.04 in (255 mm)
Operating altitude
9842.52 ft (3000 m) without derating
Net Weight
41.34 lb(US) (18.75 kg)