schneider LC1G1154EHEN

Selling Points

  • 1High Power Capability: Handles up to 250A at 440V for AC-1 applications.
  • 2Wide Voltage Range: Compatible with 48-130V AC/DC, ensuring versatility in various electrical systems.
  • 3Advanced Features: Includes built-in auxiliary contacts (NO + NC) and local contact wear diagnosis (CWD).
  • 4Durable Design: Meets 5 million cycles mechanical durability, ensuring long-term reliability.
  • 5Easy Installation: Designed for DIN rail mounting, simplifying integration into existing electrical panels.
Product Details
LC1G1154EHEN
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Giga
Product or Component Type
Contactor
Device short name
LC1G
Contactor application
Power switching
Utilisation category
AC-3<br />AC-3e<br />AC-1<br />AC-5a<br />AC-5b<br />AC-6a<br />AC-6b<br />DC-1<br />DC-3<br />DC-5
Poles description
4P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
115 A (at <140 °F (60 °C)) at <= 440 V AC-3<br />250 A (at <104 °F (40 °C)) at <= 1000 V AC-1
[Uc] control circuit voltage
48...130 V AC 50/60 Hz<br />48...130 V DC
Control circuit voltage limits
Operational: 0.8 Uc Min...1.1 Uc Max (at <140 °F (60 °C))<br />Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
250 A (at 104 °F (40 °C))
Rated breaking capacity
1040 A at 440 V
[Icw] rated short-time withstand current
1.1 kA - 10 s<br />0.64 kA - 30 s<br />0.52 kA - 1 min<br />0.4 kA - 3 min<br />0.32 kA - 10 min
Associated fuse rating
125 A aM at <= 440 V for motor<br />125 A aM at <= 690 V for motor<br />315 A gG at <= 690 V
Average impedance
0.00018 Ohm
[Ui] rated insulation voltage
1000 V
Power dissipation per pole
10 W AC-1 - Ith 250 A<br />3 W AC-3 - Ith 115 A
compatibility code
LC1G
Pole contact composition
4 NO
Auxiliary contact composition
1 NO + 1 NC
Irms rated making capacity
1560 A at 440 V
Coil technology
Built-in bidirectional peak limiting
Safety reliability level
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
8 Mcycles
inrush power in VA (50/60 Hz, AC)
640 VA
inrush power in W (DC)
445 W
hold-in power consumption in VA (50/60 Hz, AC)
18.7 VA
hold-in power consumption in W (DC)
7.8 W
Operating time
40...70 ms closing<br />15...50 ms opening
Maximum operating rate
600 cyc/h AC-3<br />600 cyc/h AC-3e<br />300 cyc/h AC-1
Connections - terminals
Power circuit: bar 2 - busbar cross section: 25 x 6 mm<br />Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²)<br />Control circuit: push-in 1 0.0003…0.004 in² (0.2…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 1 0.0004…0.004 in² (0.25…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: push-in 2 0.0008…0.002 in² (0.5…1.0 mm²) with cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: flexible with cable end
Connection pitch
1.4 in (35 mm)
Mounting Support
Plate
Standards
EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />JIS C8201-5-1<br />UL 60335-1<br />UL 60335-2-40:Annex JJ
Product Certifications
CB Scheme<br />CCC<br />cULus<br />EAC<br />CE<br />UKCA<br />EU-RO-MR by DNV-GL
Tightening torque
159.3 lbf.in (18 N.m)
Height
7.6 in (193 mm)
Width
5.6 in (143 mm)
Depth
7.6 in (193 mm)
Net Weight
9.7 lb(US) (4.4 kg)
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Ambient Air Temperature for Operation
-13…140 °F (-25…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Mechanical robustness
Vibrations 5…300 Hz 2 gn contactor open<br />Vibrations 5…300 Hz 4 gn contactor closed<br />Shocks 10 gn 11 ms contactor open<br />Shocks 15 gn 11 ms contactor closed
color
Dark grey
Protective treatment
TH
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C) at Uc

Specifications may be subject to change without notice