Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Giga
Product or Component Type
Contactor
Device short name
LC1G
Contactor application
Power switching<br />Motor control
Utilisation category
AC-1<br />AC-3<br />AC-3e<br />AC-4<br />AC-5a<br />AC-5b<br />AC-6a<br />AC-6b<br />AC-8b<br />AC-8a<br />DC-1<br />DC-3<br />DC-5
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
275 A (at <104 °F (40 °C)) at <= 1000 V AC-1<br />150 A (at <140 °F (60 °C)) at <= 440 V AC-3
[Uc] control circuit voltage
48...130 V AC 50/60 Hz<br />48...130 V DC
Control circuit voltage limits
Operational: 0.8 Uc Min...1.1 Uc Max (at <140 °F (60 °C))<br />Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
275 A (at 104 °F (40 °C))
Rated breaking capacity
1280 A at 440 V
[Icw] rated short-time withstand current
1.2 kA - 10 s<br />0.7 kA - 30 s<br />0.6 kA - 1 min<br />0.45 kA - 3 min<br />0.35 kA - 10 min
Associated fuse rating
160 A aM at <= 440 V for motor<br />160 A aM at <= 690 V for motor<br />315 A gG at <= 690 V
Average impedance
0.00018 Ohm
[Ui] rated insulation voltage
1000 V
Power dissipation per pole
10 W AC-1 - Ith 275 A<br />5 W AC-3 - Ith 150 A
compatibility code
LC1G
Pole contact composition
3 NO
Auxiliary contact composition
1 NO + 1 NC
Motor power kW
37 kW at 230 V AC 50/60 Hz (AC-3e)<br />75 kW at 400 V AC 50/60 Hz (AC-3e)<br />75 kW at 415 V AC 50/60 Hz (AC-3e)<br />90 kW at 440 V AC 50/60 Hz (AC-3e)<br />90 kW at 500 V AC 50/60 Hz (AC-3e)<br />90 kW at 690 V AC 50/60 Hz (AC-3e)<br />75 kW at 1000 V AC 50/60 Hz (AC-3e)<br />37 kW at 230 V AC 50/60 Hz (AC-3)<br />75 kW at 400 V AC 50/60 Hz (AC-3)<br />75 kW at 415 V AC 50/60 Hz (AC-3)<br />90 kW at 440 V AC 50/60 Hz (AC-3)<br />90 kW at 500 V AC 50/60 Hz (AC-3)<br />90 kW at 690 V AC 50/60 Hz (AC-3)<br />75 kW at 1000 V AC 50/60 Hz (AC-3)<br />37 kW at 230 V AC 50/60 Hz (AC-4)<br />75 kW at 400 V AC 50/60 Hz (AC-4)<br />75 kW at 415 V AC 50/60 Hz (AC-4)<br />80 kW at 440 V AC 50/60 Hz (AC-4)<br />90 kW at 500 V AC 50/60 Hz (AC-4)<br />90 kW at 690 V AC 50/60 Hz (AC-4)<br />75 kW at 1000 V AC 50/60 Hz (AC-4)
Maximum Horse Power Rating
40 hp at 200/208 V 60 Hz<br />50 hp at 230/240 V 60 Hz<br />100 hp at 460/480 V 60 Hz<br />125 hp at 575/600 V 60 Hz
Irms rated making capacity
1890 A at 440 V
Coil technology
Built-in bidirectional peak limiting
Safety reliability level
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
8 Mcycles
inrush power in VA (50/60 Hz, AC)
260 VA
inrush power in W (DC)
190 W
hold-in power consumption in VA (50/60 Hz, AC)
8.9 VA
hold-in power consumption in W (DC)
5.0 W
Operating time
40...70 ms closing<br />15...50 ms opening
Maximum operating rate
600 cyc/h AC-3<br />600 cyc/h AC-3e<br />300 cyc/h AC-1<br />150 cyc/h AC-4
Connections - terminals
Power circuit: bar 2 - busbar cross section: 25 x 6 mm<br />Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit: bolted connection<br />Control circuit: push-in 1 0.0003…0.004 in² (0.2…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 1 0.0004…0.004 in² (0.25…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: push-in 2 0.0008…0.002 in² (0.5…1.0 mm²) with cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: flexible with cable end
Connection pitch
1.4 in (35 mm)
Mounting Support
Plate
Standards
EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />JIS C8201-5-1<br />IEC 60335-1:Clause 30.2<br />IEC 60335-2-40:Annex JJ<br />UL 60335-1<br />UL 60335-2-40:Annex JJ
Product Certifications
CB Scheme<br />CCC<br />cULus<br />EAC<br />CE<br />UKCA<br />EU-RO-MR by DNV-GL
Tightening torque
159.3 lbf.in (18 N.m)
Height
10.04 in (255 mm)
Width
4.3 in (108 mm)
Depth
7.6 in (193 mm)
Net Weight
9.04 lb(US) (4.1 kg)
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Ambient Air Temperature for Operation
-13…140 °F (-25…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Mechanical robustness
Vibrations 5…300 Hz 2 gn contactor open<br />Vibrations 5…300 Hz 4 gn contactor closed<br />Shocks 10 gn 11 ms contactor open<br />Shocks 15 gn 11 ms contactor closed
color
Dark grey
Protective treatment
TH
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C) at Uc

Specifications may be subject to change without notice