schneider LC1G265EHEN

Selling Points

  • 1High reliability and durability with 5 Mcycles mechanical durability.
  • 2Advanced Local Contact Wear Diagnosis (CWD) for continuous monitoring.
  • 3Compact size (290mm x 140mm x 209mm) for panel space savings.
  • 4Multi-standard certified (CE, CB, CCC, cULus, EAC, KC, RCM, Marine).
  • 5IP2X protection with shrouds conforming to IEC 60529 and VDE 0106.
Product Details
LC1G265EHEN
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Giga
Product or Component Type
Contactor
Device short name
LC1G
Contactor application
Power switching<br />Motor control
Utilisation category
AC-1<br />AC-3<br />AC-3e<br />AC-4<br />AC-5a<br />AC-5b<br />AC-6a<br />AC-6b<br />AC-8b<br />AC-8a<br />DC-1<br />DC-3<br />DC-5
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
385 A (at <104 °F (40 °C)) at <= 1000 V AC-1<br />265 A (at <140 °F (60 °C)) at <= 440 V AC-3
[Uc] control circuit voltage
48...130 V AC 50/60 Hz<br />48...130 V DC
Control circuit voltage limits
Operational: 0.8 Uc Min...1.1 Uc Max (at <140 °F (60 °C))<br />Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
385 A (at 104 °F (40 °C))
Rated breaking capacity
2380 A at 440 V
[Icw] rated short-time withstand current
2.2 kA - 10 s<br />1.23 kA - 30 s<br />0.95 kA - 1 min<br />0.62 kA - 3 min<br />0.48 kA - 10 min
Associated fuse rating
315 A aM at <= 440 V for motor<br />250 A aM at <= 690 V for motor<br />400 A gG at <= 690 V
Average impedance
0.000144 Ohm
[Ui] rated insulation voltage
1000 V
Power dissipation per pole
20 W AC-1 - Ith 385 A<br />11 W AC-3 - Ith 265 A
compatibility code
LC1G
Pole contact composition
3 NO
Auxiliary contact composition
1 NO + 1 NC
Motor power kW
75 kW at 230 V AC 50/60 Hz (AC-3e)<br />132 kW at 400 V AC 50/60 Hz (AC-3e)<br />132 kW at 415 V AC 50/60 Hz (AC-3e)<br />160 kW at 440 V AC 50/60 Hz (AC-3e)<br />160 kW at 500 V AC 50/60 Hz (AC-3e)<br />200 kW at 690 V AC 50/60 Hz (AC-3e)<br />160 kW at 1000 V AC 50/60 Hz (AC-3e)<br />75 kW at 230 V AC 50/60 Hz (AC-3)<br />132 kW at 400 V AC 50/60 Hz (AC-3)<br />132 kW at 415 V AC 50/60 Hz (AC-3)<br />160 kW at 440 V AC 50/60 Hz (AC-3)<br />160 kW at 500 V AC 50/60 Hz (AC-3)<br />200 kW at 690 V AC 50/60 Hz (AC-3)<br />160 kW at 1000 V AC 50/60 Hz (AC-3)<br />75 kW at 230 V AC 50/60 Hz (AC-4)<br />132 kW at 400 V AC 50/60 Hz (AC-4)<br />132 kW at 415 V AC 50/60 Hz (AC-4)<br />150 kW at 440 V AC 50/60 Hz (AC-4)<br />160 kW at 500 V AC 50/60 Hz (AC-4)<br />160 kW at 690 V AC 50/60 Hz (AC-4)<br />160 kW at 1000 V AC 50/60 Hz (AC-4)
Maximum Horse Power Rating
75 hp at 200/208 V 60 Hz<br />100 hp at 230/240 V 60 Hz<br />200 hp at 460/480 V 60 Hz<br />200 hp at 575/600 V 60 Hz
Irms rated making capacity
3320 A at 440 V
Coil technology
Built-in bidirectional peak limiting
Safety reliability level
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
8 Mcycles
inrush power in VA (50/60 Hz, AC)
780 VA
inrush power in W (DC)
695 W
hold-in power consumption in VA (50/60 Hz, AC)
17.6 VA
hold-in power consumption in W (DC)
7.8 W
Operating time
40...70 ms closing<br />15...50 ms opening
Maximum operating rate
600 cyc/h AC-3<br />600 cyc/h AC-3e<br />300 cyc/h AC-1<br />150 cyc/h AC-4
Connections - terminals
Power circuit: bar 2 - busbar cross section: 32 x 10 mm<br />Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit: bolted connection<br />Control circuit: push-in 1 0.0003…0.004 in² (0.2…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 1 0.0004…0.004 in² (0.25…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: push-in 2 0.0008…0.002 in² (0.5…1.0 mm²) with cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: flexible with cable end
Connection pitch
1.8 in (45 mm)
Mounting Support
Plate
Standards
EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />JIS C8201-5-1<br />IEC 60335-1:Clause 30.2<br />IEC 60335-2-40:Annex JJ<br />UL 60335-1<br />UL 60335-2-40:Annex JJ
Product Certifications
CB Scheme<br />CCC<br />cULus<br />EAC<br />CE<br />UKCA<br />EU-RO-MR by DNV-GL
Tightening torque
309.8 lbf.in (35 N.m)
Height
8.9 in (225 mm)
Width
5.5 in (140 mm)
Depth
8.9 in (226 mm)
Net Weight
16.5 lb(US) (7.5 kg)
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Ambient Air Temperature for Operation
-13…140 °F (-25…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Mechanical robustness
Vibrations 5…300 Hz 2 gn contactor open<br />Vibrations 5…300 Hz 4 gn contactor closed<br />Shocks 10 gn 11 ms contactor open<br />Shocks 15 gn 11 ms contactor closed
color
Dark grey
Protective treatment
TH
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C) at Uc

Specifications may be subject to change without notice