schneider LC1G330BEEA

Selling Points

  • 1High Power Rating: Handles up to 330A and 185kW at 440V.
  • 2Versatile Coil: Compatible with both AC and DC coils in the 24-48V range.
  • 3Advanced Design: Built-in bidirectional peak limiting for enhanced performance.
  • 4Durable Construction: IP2X protection and robust against vibrations and shocks.
  • 5Comprehensive Certifications: Meets multiple international standards including CE, CB, and cULus.
Product Details
LC1G330BEEA
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Range of Product
TeSys Giga
Product or Component Type
Contactor
Device short name
LC1G
Contactor application
Power switching<br />Motor control
Utilisation category
AC-1<br />AC-3<br />AC-3e<br />AC-4<br />AC-5a<br />AC-5b<br />AC-6a<br />AC-6b<br />AC-8a<br />AC-8b<br />DC-1<br />DC-3<br />DC-5
Poles description
3P
[Ue] rated operational voltage
<= 1000 V AC 50/60 Hz<br /> <= 460 V DC
[Ie] rated operational current
440 A (at <104 °F (40 °C)) at <= 1000 V AC-1<br />330 A (at <140 °F (60 °C)) at <= 440 V AC-3
[Uc] control circuit voltage
24...48 V AC 50/60 Hz<br />24...48 V DC
Control circuit voltage limits
Operational: 0.8 Uc Min...1.1 Uc Max (at <140 °F (60 °C))<br />Drop-out: 0.1 Uc Max...0.45 Uc Min (at <140 °F (60 °C))
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
440 A (at 104 °F (40 °C))
Rated breaking capacity
2940 A at 440 V
[Icw] rated short-time withstand current
2.65 kA - 10 s<br />1.8 kA - 30 s<br />1.3 kA - 1 min<br />0.9 kA - 3 min<br />0.75 kA - 10 min
Associated fuse rating
400 A aM at <= 440 V for motor<br />250 A aM at <= 690 V for motor<br />500 A gG at <= 690 V
Average impedance
0.000144 Ohm
[Ui] rated insulation voltage
1000 V
Power dissipation per pole
30 W AC-1 - Ith 440 A<br />16 W AC-3 - Ith 330 A
compatibility code
LC1G
Pole contact composition
3 NO
Auxiliary contact composition
1 NO + 1 NC
Motor power kW
90 kW at 230 V AC 50/60 Hz (AC-3e)<br />160 kW at 400 V AC 50/60 Hz (AC-3e)<br />160 kW at 415 V AC 50/60 Hz (AC-3e)<br />185 kW at 440 V AC 50/60 Hz (AC-3e)<br />200 kW at 500 V AC 50/60 Hz (AC-3e)<br />220 kW at 690 V AC 50/60 Hz (AC-3e)<br />185 kW at 1000 V AC 50/60 Hz (AC-3e)<br />90 kW at 230 V AC 50/60 Hz (AC-3)<br />160 kW at 400 V AC 50/60 Hz (AC-3)<br />160 kW at 415 V AC 50/60 Hz (AC-3)<br />200 kW at 440 V AC 50/60 Hz (AC-3)<br />200 kW at 500 V AC 50/60 Hz (AC-3)<br />220 kW at 690 V AC 50/60 Hz (AC-3)<br />185 kW at 1000 V AC 50/60 Hz (AC-3)<br />90 kW at 230 V AC 50/60 Hz (AC-4)<br />160 kW at 400 V AC 50/60 Hz (AC-4)<br />160 kW at 415 V AC 50/60 Hz (AC-4)<br />185 kW at 440 V AC 50/60 Hz (AC-4)<br />200 kW at 500 V AC 50/60 Hz (AC-4)<br />220 kW at 690 V AC 50/60 Hz (AC-4)<br />185 kW at 1000 V AC 50/60 Hz (AC-4)
Maximum Horse Power Rating
100 hp at 200/208 V 60 Hz<br />125 hp at 230/240 V 60 Hz<br />250 hp at 460/480 V 60 Hz<br />300 hp at 575/600 V 60 Hz
Irms rated making capacity
3830 A at 440 V
Coil technology
Built-in bidirectional peak limiting
Safety reliability level
B10d = 400000 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 3000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
8 Mcycles
inrush power in VA (50/60 Hz, AC)
540 VA
inrush power in W (DC)
380 W
hold-in power consumption in VA (50/60 Hz, AC)
17.9 VA
hold-in power consumption in W (DC)
6.4 W
Operating time
40...70 ms closing<br />15...50 ms opening
Maximum operating rate
600 cyc/h AC-3<br />600 cyc/h AC-3e<br />300 cyc/h AC-1<br />150 cyc/h AC-4
Connections - terminals
Power circuit: bar 2 - busbar cross section: 32 x 10 mm<br />Power circuit: lugs-ring terminals 1 0.3 in² (185 mm²)<br />Power circuit: bolted connection<br />Control circuit: push-in 1 0.0003…0.004 in² (0.2…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 1 0.0004…0.004 in² (0.25…2.5 mm²) - cable stiffness: flexible with cable end<br />Control circuit: push-in 2 0.0008…0.002 in² (0.5…1.0 mm²) with cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: solid stranded without cable end<br />Control circuit: push-in 0.001…0.004 in² (0.75…2.5 mm²) - cable stiffness: flexible with cable end
Connection pitch
1.8 in (45 mm)
Mounting Support
Plate
Standards
EN/IEC 60947-4-1<br />EN/IEC 60947-5-1<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />JIS C8201-5-1<br />IEC 60335-1:Clause 30.2<br />IEC 60335-2-40:Annex JJ<br />UL 60335-1<br />UL 60335-2-40:Annex JJ
Product Certifications
CB Scheme<br />CCC<br />cULus<br />EAC<br />CE<br />UKCA<br />EU-RO-MR by DNV-GL
Tightening torque
309.8 lbf.in (35 N.m)
Height
11.4 in (290 mm)
Width
5.5 in (140 mm)
Depth
8.9 in (226 mm)
Net Weight
18.08 lb(US) (8.2 kg)
IP degree of protection
IP2X front face with shrouds IEC 60529<br />IP2X front face with shrouds VDE 0106
Ambient Air Temperature for Operation
-13…140 °F (-25…60 °C)
Ambient Air Temperature for Storage
-76…176 °F (-60…80 °C)
Mechanical robustness
Vibrations 5…300 Hz 2 gn contactor open<br />Vibrations 5…300 Hz 4 gn contactor closed<br />Shocks 10 gn 11 ms contactor open<br />Shocks 15 gn 11 ms contactor closed
color
Dark grey
Protective treatment
TH
Permissible ambient air temperature around the device
-40…158 °F (-40…70 °C) at Uc