schneider LC1K09008B7TQ

Selling Points

  • 1High Reliability: Built to last with a mechanical durability of 10 Mcycles.
  • 2Versatile Control: Features 2 NO and 2 NC contacts for flexible control options.
  • 3Wide Voltage Compatibility: Operates at 24V AC control circuit voltage.
  • 4Robust Design: Rated breaking capacity of 110 kA at 440V.
  • 5Compliance and Certifications: Meets international standards including EN/IEC 60947-4-1 and UL 60947-4-1.
Product Details
LC1K09008B7TQ
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Product or Component Type
Contactor
Device short name
LC1K
Contactor application
Resistive load
Utilisation category
AC-1
Poles description
4P
power pole contact composition
2 NO + 2 NC
[Ue] rated operational voltage
Power circuit <= 690 V AC <= 400 Hz<br />Signalling circuit <= 690 V AC <= 400 Hz
[Ie] rated operational current
20 A (at <140 °F (60 °C)) at <= 690 V AC AC-1 for power circuit
Control circuit type
AC 50/60 Hz standard
[Uc] control circuit voltage
24 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ith] conventional free air thermal current
20 A (at 140 °F (60 °C)) for power circuit<br />10 A (at 122 °F (50 °C)) for signalling circuit
Irms rated making capacity
110 A AC for power circuit conforming to IEC 60947
Rated breaking capacity
110 A at 220...230 V conforming to IEC 60947<br />110 A at 380...400 V conforming to IEC 60947<br />110 A at 415 V conforming to IEC 60947<br />110 A at 440 V conforming to IEC 60947<br />80 A at 500 V conforming to IEC 60947<br />70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current
90 A 122 °F (50 °C) - 1 s for power circuit<br />85 A 122 °F (50 °C) - 5 s for power circuit<br />80 A 122 °F (50 °C) - 10 s for power circuit<br />60 A 122 °F (50 °C) - 30 s for power circuit<br />45 A 122 °F (50 °C) - 1 min for power circuit<br />40 A 122 °F (50 °C) - 3 min for power circuit<br />20 A 122 °F (50 °C) - >= 15 min for power circuit
Associated fuse rating
10 A gG for control circuit conforming to IEC 60947<br />10 A gG for control circuit conforming to VDE 0660<br />25 A gG at <= 440 V for power circuit
Average impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltage
Control circuit 690 V BS 5424<br />Control circuit 690 V IEC 60947<br />Power circuit 690 V BS 5424<br />Power circuit 690 V IEC 60947<br />Power circuit 690 V NF C 20-040<br />Control circuit 750 V VDE 0110 group C<br />Power circuit 750 V VDE 0110 group C<br />Control circuit 600 V CSA C22.2 No 14<br />Power circuit 600 V UL 508 CSA C22.2 No 14
Insulation resistance
> 10 MOhm for control circuit
Inrush power in VA
30 VA (at 68 °F (20 °C))
Hold-in power consumption in VA
4.5 VA 50/60 Hz (at 68 °F (20 °C))
Control circuit voltage limits
Operational: 0.8...1.15 Uc at 50/60 Hz (at <122 °F (50 °C))<br />Drop-out: >= 0.20 Uc at 50/60 Hz (at <122 °F (50 °C))
Connections - terminals
screw clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid<br /> screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end<br /> screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end<br /> screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid<br /> screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end<br /> screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end
Maximum operating rate
3600 cyc/h
Coil technology
Without built-in bidirectional peak limiting diode suppressor
Minimum switching current
5 mA for control circuit
Minimum switching voltage
17 V for control circuit
Mounting Support
Rail<br />Plate
Operating time
10...20 ms coil de-energisation and NO opening<br />15...25 ms coil de-energisation and NC opening<br />10...20 ms between energisation of coil and closing of NO contact<br />5...15 ms coil energisation and NC opening
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10 Mcycles
Electrical durability
0.16 Mcycles 20 A AC-1 <= 690 V
Height
2.3 in (58 mm)
Width
1.8 in (45 mm)
Depth
2.2 in (57 mm)
Net Weight
0.40 lb(US) (0.18 kg)
Standards
EN/IEC 60947-4-1<br />GB/T 14048.4<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1
Product Certifications
CB Scheme<br />CCC<br />UL<br />CSA<br />EAC<br />CE<br />UKCA
Ambient Air Temperature for Storage
-58…176 °F (-50…80 °C)
Operating altitude
6561.68 ft (2000 m) without derating
Fire resistance
1562 °F (850 °C) IEC 60695-2-1
Flame retardance
Class C2 conforming to NF F 16-101<br />Class C2 conforming to NF F 16-102<br />V1 conforming to UL 94

Specifications may be subject to change without notice