schneider LC1K09017B7

Selling Points

  • 1High Reliability: Designed for 600 cycles/hour and up to 50°C, ensuring consistent performance in demanding environments.
  • 2Compact Design: Very compact (45mm width) with DIN-rail mounting or screw fixing options.
  • 3Multi-Standard Certified: Meets IEC, UL, CSA, CCC, and EAC standards for global compatibility.
  • 4Green Premium Compliant: RoHS and REACh compliant, supporting sustainable practices.
  • 5Easy Integration: Includes a 24V AC coil and 1 NC auxiliary contact for seamless integration into control systems.
Product Details
LC1K09017B7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range
TeSys
Product or Component Type
Contactor
Device short name
LC1K
Device Application
Control
Contactor application
Motor control<br />Resistive load
Utilisation category
AC-3<br />AC-3e<br />AC-1<br />AC-4
Poles description
3P
power pole contact composition
3 NO
[Ue] rated operational voltage
Power circuit <= 690 V AC <= 400 Hz<br />Signalling circuit <= 690 V AC <= 400 Hz
[Ie] rated operational current
9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3 for power circuit<br />9 A (at <140 °F (60 °C)) at <= 440 V AC AC-3e for power circuit<br />20 A (at <140 °F (60 °C)) at <= 690 V AC AC-1 for power circuit
Control circuit type
AC 50/60 Hz
[Uc] control circuit voltage
24 V AC 50/60 Hz
Motor power kW
2.2 kW 220...230 V AC 50/60 Hz AC-3<br />4 kW 380...415 V AC 50/60 Hz AC-3<br />4 kW 440/690 V AC 50/60 Hz AC-3<br />2.2 kW 220...230 V AC 50/60 Hz AC-3e<br />4 kW 380...415 V AC 50/60 Hz AC-3e<br />4 kW 440/690 V AC 50/60 Hz AC-3e<br />2.2 kW 220...230 V AC 50/60 Hz AC-4<br />4 kW 380...415 V AC 50/60 Hz AC-4<br />4 kW 440/690 V AC 50/60 Hz AC-4
Auxiliary contact composition
1 NC
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
[Ith] conventional free air thermal current
20 A (at 140 °F (60 °C)) for power circuit<br />10 A (at 122 °F (50 °C)) for signalling circuit
Irms rated making capacity
110 A AC for power circuit conforming to IEC 60947<br />110 A AC for signalling circuit conforming to IEC 60947
Rated breaking capacity
110 A at 220...230 V conforming to IEC 60947<br />110 A at 380...400 V conforming to IEC 60947<br />110 A at 415 V conforming to IEC 60947<br />110 A at 440 V conforming to IEC 60947<br />80 A at 500 V conforming to IEC 60947<br />70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current
90 A 122 °F (50 °C) - 1 s for power circuit<br />85 A 122 °F (50 °C) - 5 s for power circuit<br />80 A 122 °F (50 °C) - 10 s for power circuit<br />60 A 122 °F (50 °C) - 30 s for power circuit<br />45 A 122 °F (50 °C) - 1 min for power circuit<br />40 A 122 °F (50 °C) - 3 min for power circuit<br />20 A 122 °F (50 °C) - >= 15 min for power circuit<br />80 A - 1 s for signalling circuit<br />90 A - 500 ms for signalling circuit<br />110 A - 100 ms for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Control circuit voltage limits
Operational: 0.8...1.15 Uc (at <122 °F (50 °C))<br />Drop-out: >= 0.20 Uc (at <122 °F (50 °C))
Connections - terminals
Faston terminals 2 0.1 in (2.8 mm)) <br /> Faston terminals 1 0.25 in (6.35 mm))
Maximum operating rate
3600 cyc/h
Auxiliary contacts type
Instantaneous 1 NC
Signalling circuit frequency
<= 400 Hz
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Mounting Support
Rail<br />Plate
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Non overlap distance
0.02 in (0.5 mm)
Mechanical durability
10 Mcycles
Electrical durability
1.3 Mcycles 9 A AC-3 <= 440 V<br />1.3 Mcycles 9 A AC-3e <= 440 V<br />0.16 Mcycles 20 A AC-1 <= 690 V<br />0.02 Mcycles 54 A AC-4 <= 440 V
Mechanical robustness
Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27<br />Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6<br />Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Height
2.3 in (58 mm)
Width
1.8 in (45 mm)
Depth
2.2 in (57 mm)
Net Weight
0.40 lb(US) (0.18 kg)
Standards
EN/IEC 60947-4-1<br />GB/T 14048.4<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1<br />IEC 60335-1:Clause 30.2<br />IEC 60335-2-40:Annex JJ<br />UL 60335-2-40:Annex JJ
Product Certifications
CB Scheme<br />CCC<br />UL<br />CSA<br />EAC<br />CE<br />UKCA
Ambient Air Temperature for Storage
-58…176 °F (-50…80 °C)
Flame retardance
V1 conforming to UL 94<br />Requirement 2 conforming to NF F 16-101<br />Requirement 2 conforming to NF F 16-102