Product Model
LC1K12017G7

Selling Points
- 1Compact design for efficient motor control.
- 2Rated for 12A AC-3, suitable for various motor applications.
- 3Includes 1 NC auxiliary contact for additional functionality.
- 4Compatible with 120VAC coil for easy integration.
- 5Meets international standards including UL, CSA, and UKCA.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | TeSys K | Range | TeSys |
Product name | TeSys K | Device Application | Control |
Product or Component Type | Contactor | Device short name | LC1K |
Utilisation category | AC-3<br />AC-4<br />AC-1 | Poles description | 3P |
Pole contact composition | 3 NO | [Ie] rated operational current | 20 A (at <122 °F (50 °C)) at <= 440 V AC AC-1 for power circuit<br />12 A at <= 440 V AC AC-3 for power circuit<br />16 A (at <158 °F (70 °C)) at 690 V AC AC-1 for power circuit |
[Uc] control circuit voltage | 120 V AC 50/60 Hz | Signalling circuit frequency | <= 400 Hz |
Non overlap distance | 0.02 in (0.5 mm) | Contactor application | Resistive load<br />Motor control |
Auxiliary contact composition | 1 NC | Control circuit voltage limits | Operational: 0.8...1.15 Uc (at <122 °F (50 °C))<br />Drop-out: 0.2...0.75 Uc (at <122 °F (50 °C)) |
Control circuit type | AC 50/60 Hz | Mechanical robustness | Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27<br />Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6<br />Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6 |
Standards | EN/IEC 60947-4-1<br />GB/T 14048.4<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1 | Protective treatment | TC IEC 60068<br />TC DIN 50016 |
Overvoltage category | III | Product Certifications | CB Scheme<br />CCC<br />UL<br />CSA<br />EAC<br />CE<br />UKCA |
Operating altitude | 6561.68 ft (2000 m) without derating | [Ith] conventional free air thermal current | 20 A (at 122 °F (50 °C)) for power circuit<br />10 A (at 122 °F (50 °C)) for signalling circuit |
Irms rated making capacity | 110 A AC for signalling circuit conforming to IEC 60947<br />144 A AC for power circuit conforming to NF C 63-110<br />144 A AC for power circuit conforming to IEC 60947 | Rated breaking capacity | 110 A at 440 V conforming to IEC 60947<br />80 A at 500 V conforming to IEC 60947<br />70 A at 660...690 V conforming to IEC 60947 |
Associated fuse rating | 25 A gG at <= 440 V for power circuit<br />25 A aM for power circuit<br />10 A gG for signalling circuit conforming to IEC 60947<br />10 A gG for signalling circuit conforming to VDE 0660 | Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
Inrush power in VA | 30 VA (at 68 °F (20 °C)) | Hold-in power consumption in VA | 4.5 VA (at 68 °F (20 °C)) |
Operating time | 10...20 ms coil de-energisation and NO opening<br />10...20 ms coil energisation and NO closing | Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Maximum operating rate | 3600 cyc/h | Minimum switching current | 5 mA for signalling circuit |
Minimum switching voltage | 17 V for signalling circuit | Insulation resistance | > 10 MOhm for signalling circuit |
Height | 2.3 in (58 mm) | Width | 1.8 in (45 mm) |
Depth | 2.2 in (57 mm) | compatibility code | LC1K |
Motor power kW | 4 kW 480 V AC 50/60 Hz<br />4 kW 500...600 V AC 50/60 Hz<br />4 kW 660...690 V AC 50/60 Hz<br />3 kW 220...230 V AC 50/60 Hz<br />5.5 kW 380...415 V AC 50/60 Hz<br />5.5 kW 440 V AC 50/60 Hz | Heat dissipation | 1.3 W |
Flame retardance | V1 conforming to UL 94<br />Requirement 2 conforming to NF F 16-101<br />Requirement 2 conforming to NF F 16-102 |
Specifications may be subject to change without notice