schneider LC7K090045M7

Selling Points

  • 12.28 in H x 3.54 in W x 2.24 in D dimensions for space-saving installation.
  • 2Provides flexibility in selecting components that meet or exceed desired SCCR.
  • 3Finger-safe terminals with North American and international markings for enhanced safety.
  • 4220 to 230 VAC coil voltage and 50/60 Hz frequency rating for versatile use.
  • 5Mountable on 35 mm DIN rail or panel mount with screws for convenient setup.
Product Details
LC7K090045M7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
TeSys K
Range
TeSys
Product name
TeSys K
Device Application
Control
Product or Component Type
Contactor
Device short name
LC7K
Utilisation category
AC-1
Poles description
4P
Pole contact composition
4 NO
[Ie] rated operational current
20 A (at <122 °F (50 °C)) at <= 440 V AC AC-1 for power circuit<br />16 A (at <158 °F (70 °C)) at 690 V AC AC-1 for power circuit
Signalling circuit frequency
<= 400 Hz
Contactor application
Resistive load
Control circuit voltage limits
Operational: 0.85...1.1 Uc (at <122 °F (50 °C))<br />Drop-out: 0.1...0.75 Uc (at <122 °F (50 °C))
Control circuit type
AC 50/60 Hz silent
[Uc] control circuit voltage
220...230 V AC 50/60 Hz
Connections - terminals
solder pins 1.5 x 0.9 mm
Electrical durability
0.18 Mcycles 20 A AC-1 <= 440 V
Mechanical robustness
Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27<br />Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6<br />Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Standards
EN/IEC 60947-4-1<br />GB/T 14048.4<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1
IP degree of protection
IP2X VDE 0106
Protective treatment
TC IEC 60068<br />TC DIN 50016
[Ui] rated insulation voltage
Power circuit 600 V UL 508<br />Power circuit 690 V IEC 60947-4-1<br />Power circuit 600 V CSA C22.2 No 14
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
Mounting Support
Printed circuit boards
Product Certifications
CB Scheme<br />CCC<br />UL<br />CSA<br />EAC<br />CE<br />UKCA
Ambient Air Temperature for Storage
-58…176 °F (-50…80 °C)
Operating altitude
6561.68 ft (2000 m) without derating
[Ue] rated operational voltage
Power circuit 690 V AC 50/60 Hz
[Ith] conventional free air thermal current
20 A (at 122 °F (50 °C)) for power circuit
Irms rated making capacity
110 A AC for power circuit conforming to NF C 63-110<br />110 A AC for power circuit conforming to IEC 60947
Rated breaking capacity
110 A at 415 V conforming to IEC 60947<br />110 A at 440 V conforming to IEC 60947<br />80 A at 500 V conforming to IEC 60947<br />110 A at 220...230 V conforming to IEC 60947<br />110 A at 380...400 V conforming to IEC 60947<br />70 A at 660...690 V conforming to IEC 60947
Associated fuse rating
25 A gG at <= 440 V for power circuit<br />25 A aM for power circuit
Average impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
Inrush power in VA
3 VA (at 68 °F (20 °C))
Hold-in power consumption in VA
3 VA (at 68 °F (20 °C))
Operating time
30...40 ms coil energisation and NO closing<br />30 ms coil de-energisation and NO opening
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10 Mcycles
Maximum operating rate
3600 cyc/h
Height
2.3 in (58 mm)
Width
1.8 in (45 mm)
Depth
2.2 in (57 mm)
Net Weight
0.496 lb(US) (0.225 kg)
compatibility code
LC7K
[Icw] rated short-time withstand current
90 A 122 °F (50 °C) - 1 s for power circuit<br />85 A 122 °F (50 °C) - 5 s for power circuit<br />80 A 122 °F (50 °C) - 10 s for power circuit<br />60 A 122 °F (50 °C) - 30 s for power circuit<br />45 A 122 °F (50 °C) - 1 min for power circuit<br />40 A 122 °F (50 °C) - 3 min for power circuit<br />20 A 122 °F (50 °C) - >= 15 min for power circuit
Heat dissipation
3 W
Flame retardance
V1 conforming to UL 94<br />Requirement 2 conforming to NF F 16-101<br />Requirement 2 conforming to NF F 16-102