schneider LC7K09107B7

Selling Points

  • 1AC-3 Rating Up to 440V: Designed for high-voltage applications.
  • 29A Current Capacity: Handles significant electrical loads.
  • 31 NO Auxiliary Contact: Includes a built-in auxiliary contact for added functionality.
  • 424VAC Coil: Compatible with standard 24VAC control systems.
  • 5Durable Construction: Built to withstand industrial environments with shock resistance.
Product Details
LC7K09107B7
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
TeSys K
Range
TeSys
Product name
TeSys K
Device Application
Control
Product or Component Type
Contactor
Device short name
LC7K
Utilisation category
AC-3<br />AC-1<br />AC-4
Poles description
3P
Pole contact composition
3 NO
[Ie] rated operational current
20 A (at <122 °F (50 °C)) at <= 440 V AC AC-1 for power circuit<br />9 A at <= 440 V AC AC-3 for power circuit<br />16 A (at <158 °F (70 °C)) at 690 V AC AC-1 for power circuit
[Uc] control circuit voltage
24 V AC 50/60 Hz
Signalling circuit frequency
<= 400 Hz
Non overlap distance
0.02 in (0.5 mm)
Contactor application
Motor control<br />Resistive load
Auxiliary contact composition
1 NO
Control circuit voltage limits
Operational: 0.85...1.1 Uc (at <122 °F (50 °C))<br />Drop-out: 0.1...0.75 Uc (at <122 °F (50 °C))
Control circuit type
AC 50/60 Hz silent
Connections - terminals
Faston terminals 2 2.8 mm<br /> Faston terminals 1 6.35 mm
Electrical durability
0.18 Mcycles 20 A AC-1 <= 440 V<br />1.3 Mcycles 9 A AC-3 <= 440 V
Mechanical robustness
Shocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27<br />Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27<br />Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6<br />Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Standards
EN/IEC 60947-4-1<br />GB/T 14048.4<br />UL 60947-4-1<br />CSA C22.2 No 60947-4-1<br />JIS C8201-4-1
IP degree of protection
IP2X VDE 0106
Protective treatment
TC IEC 60068<br />TC DIN 50016
[Ui] rated insulation voltage
Power circuit 600 V UL 508<br />Power circuit 690 V IEC 60947-4-1<br />Signalling circuit 690 V IEC 60947-4-1<br />Signalling circuit 690 V IEC 60947-5-1<br />Signalling circuit 600 V UL 508<br />Power circuit 600 V CSA C22.2 No 14<br />Signalling circuit 600 V CSA C22.2 No 14
[Uimp] rated impulse withstand voltage
8 kV
Overvoltage category
III
Mounting Support
Plate<br />Rail
Product Certifications
CB Scheme<br />CCC<br />UL<br />CSA<br />EAC<br />CE<br />UKCA
Ambient Air Temperature for Storage
-58…176 °F (-50…80 °C)
Operating altitude
6561.68 ft (2000 m) without derating
[Ue] rated operational voltage
Power circuit 690 V AC 50/60 Hz<br />Signalling circuit <= 690 V AC 50/60 Hz
[Ith] conventional free air thermal current
20 A (at 122 °F (50 °C)) for power circuit<br />10 A (at 122 °F (50 °C)) for signalling circuit
Irms rated making capacity
110 A AC for power circuit conforming to NF C 63-110<br />110 A AC for power circuit conforming to IEC 60947<br />110 A AC for signalling circuit conforming to IEC 60947
Rated breaking capacity
110 A at 415 V conforming to IEC 60947<br />110 A at 440 V conforming to IEC 60947<br />80 A at 500 V conforming to IEC 60947<br />110 A at 220...230 V conforming to IEC 60947<br />110 A at 380...400 V conforming to IEC 60947<br />70 A at 660...690 V conforming to IEC 60947
Associated fuse rating
25 A gG at <= 440 V for power circuit<br />25 A aM for power circuit<br />10 A gG for signalling circuit conforming to IEC 60947<br />10 A gG for signalling circuit conforming to VDE 0660
Average impedance
3 mOhm - Ith 20 A 50 Hz for power circuit
Inrush power in VA
3 VA (at 68 °F (20 °C))
Hold-in power consumption in VA
3 VA (at 68 °F (20 °C))
Operating time
30...40 ms coil energisation and NO closing<br />30 ms coil de-energisation and NO opening
Safety reliability level
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1<br />B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Mechanical durability
10 Mcycles
Maximum operating rate
3600 cyc/h
Minimum switching current
5 mA for signalling circuit
Minimum switching voltage
17 V for signalling circuit
Insulation resistance
> 10 MOhm for signalling circuit
Height
2.3 in (58 mm)
Width
1.8 in (45 mm)
Depth
2.2 in (57 mm)
Net Weight
0.496 lb(US) (0.225 kg)
compatibility code
LC7K
Motor power kW
4 kW 480 V AC 50/60 Hz<br />4 kW 500...600 V AC 50/60 Hz<br />4 kW 660...690 V AC 50/60 Hz<br />2.2 kW 220...230 V AC 50/60 Hz<br />4 kW 380...415 V AC 50/60 Hz<br />4 kW 440 V AC 50/60 Hz
[Icw] rated short-time withstand current
90 A 122 °F (50 °C) - 1 s for power circuit<br />85 A 122 °F (50 °C) - 5 s for power circuit<br />80 A 122 °F (50 °C) - 10 s for power circuit<br />60 A 122 °F (50 °C) - 30 s for power circuit<br />45 A 122 °F (50 °C) - 1 min for power circuit<br />40 A 122 °F (50 °C) - 3 min for power circuit<br />20 A 122 °F (50 °C) - >= 15 min for power circuit<br />80 A - 1 s for signalling circuit<br />90 A - 500 ms for signalling circuit<br />110 A - 100 ms for signalling circuit
Heat dissipation
3 W
Flame retardance
V1 conforming to UL 94<br />Requirement 2 conforming to NF F 16-101<br />Requirement 2 conforming to NF F 16-102

Specifications may be subject to change without notice