schneider RM35JA32MR

Selling Points

  • 1High Accuracy and Predictive Maintenance: Experience unprecedented accuracy and predictive maintenance with the RM35JA32MR.
  • 2Versatile Voltage Range: Compatible with 24VDC/240VAC coil voltage, making it suitable for various applications.
  • 3Compact Design: Simplified panel design with a 35mm width, similar to a 3-pole circuit breaker, for easier installation.
  • 4LED Display and Fault Identification: Equipped with an LED display for quick fault identification and troubleshooting.
  • 5Durable and Reliable: Meets stringent safety standards, including CSA, CE, and UL certifications, ensuring long-lasting performance.
Product Details
RM35JA32MR
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Harmony Control Relays
Relay Type
Current control relay
Product or Component Type
Current control relay
Relay name
RM35JA
Relay monitored parameters
Overcurrent or undercurrent in window mode<br />Overcurrent or undercurrent detection
time delay
Adjustable 0.1...30 s, +/- 10 % of the full scale value Tt- time delay upon fault
Switching capacity in VA
2000 VA
Minimum switching current
10 mA 5 V DC
Maximum switching current
8 A AC
Maximum power consumption in VA
3.5 VA
Measurement range
150 mA...15 A AC/DC
Utilisation category
AC-15 IEC 60947-5-1<br />DC-13 IEC 60947-5-1<br />AC-1 IEC 60947-4-1<br />DC-1 IEC 60947-4-1
Contacts type and composition
2 C/O
Reset time
1500 ms at maximum voltage
Maximum switching voltage
250 V AC
Supply voltage limits
20.4…264 V AC/DC
operating voltage tolerance
- 15 % + 10 % Un
Maximum power consumption in W
1.5 W DC
Resistance across terminals
0.005 Ohm E3-M terminals<br />0.015 Ohm E2-M terminals<br />0.05 Ohm E1-M terminals
Output contacts
2 C/O
Nominal output current
8 A
Maximum measuring cycle
100 ms measurement cycle as true rms value
Internal input resistance
0.015 Ohm<br />0.005 Ohm<br />0.05 Ohm
Setting accuracy of the switching threshold
+/- 10 % of the full scale
Switching threshold drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature<br /><= 1 % within the supply voltage range
Setting accuracy of time delay
10 P
Time delay drift
<= 0.05 % per degree centigrade depending permissible ambient air temperature<br /><= 1 % within the supply voltage range
Hysteresis
5…50 % adjustable threshold setting<br />3 % fixed full scale for window mode
delay at power up
0.3 s
Repeat accuracy
+/- 0.5 % input and measurement circuit<br />+/- 2 % time delay
Measurement error
< 1 % over the whole range with voltage variation<br />0.05 %/°C with temperature variation
Response time
<= 500 ms (on crossing the threshold)
Threshold setting
10...100 %
Overvoltage category
III IEC 60664-1<br />III UL 508
Insulation resistance
> 100 MOhm 500 V DC IEC 60255-27
Insulation
Between supply and measurement
Connections - terminals
Screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end<br />Screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end<br />Screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end<br />Screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Tightening torque
5.3…8.9 lbf.in (0.6…1 N.m) IEC 60947-1
Housing material
Self-extinguishing plastic
Local signalling
for relay ON LED (yellow)<br /> for power ON LED (green)
Mounting support
35 mm DIN rail conforming to IEC 60715
Electrical durability
100000 cycles
Mechanical durability
10000000 cycles
[Un] rated nominal voltage
24...240 V AC/DC 50/60 Hz, non self-powered
Safety reliability data
MTTFd = 296.8 years<br />B10d = 270000
Contacts material
Cadmium free
Width
1.4 in (35 mm)
Control Type
With test button
Net Weight
0.26 lb(US) (0.12 kg)
Immunity to microbreaks
50 ms
Electromagnetic compatibility
Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1<br />Immunity for industrial environments conforming to IEC 61000-6-2<br />Emission standard for industrial environments conforming to IEC 61000-6-4<br />Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2<br />Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2<br />Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3<br />Electrical fast transient/burst immunity test - test level: 4 kV level 4 (direct) conforming to IEC 61000-4-4<br />Electrical fast transient/burst immunity test - test level: 2 kV level 4 (capacitive coupling) conforming to IEC 61000-4-4<br />Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5<br />Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5<br />Conducted and radiated emissions class B group 1 conforming to CISPR 11<br />Conducted and radiated emissions class B conforming to CISPR 22<br />Emission standard for residential, commercial and light-industrial environments (except radiated emission) conforming to IEC 61000-6-3
Standards
IEC 60255-1
Product Certifications
CE<br />GL<br />CCC<br />EAC<br />RCM<br />UL<br />CSA
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Ambient air temperature for operation
-4…122 °F (-20…50 °C) 60 Hz<br /> -4…140 °F (-20…60 °C) 50 Hz
Environmental characteristic
3K3 C
Relative humidity
93…97 % 77…131 °F (25…55 °C) IEC 60068-2-30
Vibration resistance
0.075 mm 10…58.1 Hz) not in operation IEC 60068-2-6<br />1 gn 10…58.1 Hz) not in operation IEC 60068-2-6<br />0.035 mm 58.1…150 Hz) in operation IEC 60068-2-6<br />0.5 gn 58.1…150 Hz) in operation IEC 60068-2-6
Shock resistance
15 gn 11 ms) not in operation IEC 60068-2-27<br />5 gn 11 ms) in operation IEC 60068-2-27
IP degree of protection
IP20 IEC 60529 terminals)<br />IP50 IEC 60529 front panel)<br />IP30 IEC 60529 housing)
Pollution degree
3 IEC 60664-1<br />3 UL 508
Dielectric test voltage
2.5 kV AC 50 Hz, 1 min IEC 60255-27

Specifications may be subject to change without notice