schneider RM4JA32Q

Selling Points

  • 1The RM4JA32Q offers precise current measurement with a range of 0.3 to 15 A, ensuring reliable operation in industrial settings.
  • 2Equipped with overcurrent detection, this relay protects your system from potential damage caused by excessive current flow.
  • 3Compatible with various voltage ranges including 110-130 V AC, 220-240 V AC, and 380-415 V AC, making it adaptable to diverse applications.
  • 4Built with robust industrial-grade components, the RM4JA32Q withstands harsh environments and ensures long-lasting performance.
  • 5Available for fast delivery worldwide, with secure payment options including major credit cards, PayPal, and more.
Product Details
RM4JA32Q
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Harmony Relay
Relay Type
Current measurement relay
Product or Component Type
Industrial measurement and control relays
Relay name
RM4J
Relay monitored parameters
Overcurrent or undercurrent detection
time delay
Adjustable 0.05...30 s
Maximum power consumption in VA
3 VA AC
Measurement range
1...5 A current AC<br />1...5 A current DC<br />3...15 A current AC<br />3...15 A current DC<br />300...1500 mA current AC<br />300...1500 mA current DC
Contacts type and composition
2 C/O
Maximum switching voltage
440 V AC
operating voltage tolerance
0.85...1.1 Uc
Output contacts
2 C/O
Maximum measuring cycle
80 ms
Internal input resistance
0.02 Ohm<br />0.006 Ohm<br />0.06 Ohm
Permissible continuous overload
20 A<br />2 A<br />7 A
Permissible non repetitive overload
10 A <= 3 s<br />100 A<br />15 A
Setting accuracy of the switching threshold
+/-5 %
Switching threshold drift
<= 0.06 % per degree centigrade depending permissible ambient air temperature<br /><= 0.5 % within the supply voltage range (0.85...1.1 Un)
Setting accuracy of time delay
10 P
Time delay drift
<= 0.07 % per degree centigrade depending on temperature<br /><= 0.5 % within the supply voltage range (0.85...1.1 Un)
Hysteresis
5…30 % adjustable current threshold setting
marking
CE : LVD 73/23/EEC<br />CE : EMC 89/336/EEC
Overvoltage category
III IEC 60664-1
[Ui] rated insulation voltage
500 V IEC
Supply disconnection value
> 0.1 Uc
Operating position
Any position without derating
Connections - terminals
Screw terminals, 2 x 1.5 mm²flexible with cable end<br />Screw terminals, 2 x 2.5 mm²flexible without cable end
Tightening torque
5.3…9.7 lbf.in (0.6…1.1 N.m)
Mechanical durability
30000000 cycles
[Ith] conventional free air thermal current
8 A
[Ie] rated operational current
2 A 24 V DC-13 158 °F (70 °C) IEC 60947-5-1/1991<br />2 A 24 V DC-13 158 °F (70 °C) VDE 0660<br />3 A 115 V AC-15 158 °F (70 °C) IEC 60947-5-1/1991<br />3 A 115 V AC-15 158 °F (70 °C) VDE 0660<br />3 A 24 V AC-15 158 °F (70 °C) IEC 60947-5-1/1991<br />3 A 24 V AC-15 158 °F (70 °C) VDE 0660<br />3 A 250 V AC-15 158 °F (70 °C) IEC 60947-5-1/1991<br />3 A 250 V AC-15 158 °F (70 °C) VDE 0660<br />0.1 A 250 V DC-13 158 °F (70 °C) IEC 60947-5-1/1991<br />0.1 A 250 V DC-13 158 °F (70 °C) VDE 0660<br />0.3 A 115 V DC-13 158 °F (70 °C) IEC 60947-5-1/1991<br />0.3 A 115 V DC-13 158 °F (70 °C) VDE 0660
Switching capacity in mA
10 mA 12 V
Switching voltage
250 V AC
Contacts material
90/10 silver nickel contacts
Number of cables
2
Width
1.8 in (45 mm)
Height
3.07 in (78 mm)
Depth
3.1 in (80 mm)
Terminals description ISO n°1
(15-16-18)OC<br />(25-26-28)OC<br />(C-B1-B2-B3)CO<br />(A1-A2)CO
Output relay state
Tripped if A measured > A set<br />Tripped if V measured > V set
9 mm pitches
5
Net Weight
0.450 lb(US) (0.204 kg)
Electromagnetic compatibility
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2<br />Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Standards
EN/IEC 60255-6
Product Certifications
CSA<br />GL<br />UL
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient air temperature for operation
-4…149 °F (-20…65 °C)
Environmental characteristic
3K3
Relative humidity
15…85 % IEC 60721-3-3
Shock resistance
15 gn 11 ms IEC 60255-21-1
IP degree of protection
IP20 IEC 60529 terminals)<br />IP50 IEC 60529 casing)
Pollution degree
3 IEC 60664-1
Dielectric test voltage
2.5 kV
Non-dissipating shock wave
4.8 kV
Resistance to electrostatic discharge
6 kV contact IEC 61000-4-2 level 3<br />8 kV air IEC 61000-4-2 level 3
Resistance to electromagnetic fields
9.1 V/m (10 V/m) IEC 61000-4-3 level 3
Resistance to fast transients
2 kV IEC 61000-4-4 level 3
Protection against electric shocks
2 kV level 3 IEC 61000-4-5
Disturbance radiated/conducted
CISPR 22 - class A<br />CISPR 11 group 1 - class A

Specifications may be subject to change without notice