Product Model
RM4TU02

Selling Points
- 1Three-phase network control relay for precise industrial automation.
- 2DPDT contacts ensure reliable switching operations.
- 390/10 silver nickel contacts provide high durability and performance.
- 4Operates within 300-430V range, suitable for various industrial applications.
- 5Compact design with a width of 225 mm, easy to integrate into control systems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Harmony Relay | Relay Type | Control relay |
Product Specific Application | For 3-phase supply | Relay name | RM4-T |
Relay monitored parameters | Phase sequence<br />Undervoltage detection<br />Phase failure detection | time delay | Without |
Output contacts | 2 C/O | Contacts type and composition | 2 C/O |
Poles description | 3P | [Ie] rated operational current | 2 A 158 °F (70 °C) 24 V DC-13 IEC 60947-5-1/1991<br />2 A 158 °F (70 °C) 24 V DC-13 VDE 0660<br />3 A 158 °F (70 °C) 115 V AC-15 IEC 60947-5-1/1991<br />3 A 158 °F (70 °C) 115 V AC-15 VDE 0660<br />3 A 158 °F (70 °C) 24 V AC-15 IEC 60947-5-1/1991<br />3 A 158 °F (70 °C) 24 V AC-15 VDE 0660<br />3 A 158 °F (70 °C) 250 V AC-15 IEC 60947-5-1/1991<br />3 A 158 °F (70 °C) 250 V AC-15 VDE 0660<br />0.1 A 158 °F (70 °C) 250 V DC-13 IEC 60947-5-1/1991<br />0.1 A 158 °F (70 °C) 250 V DC-13 VDE 0660<br />0.3 A 158 °F (70 °C) 115 V DC-13 IEC 60947-5-1/1991<br />0.3 A 158 °F (70 °C) 115 V DC-13 VDE 0660 |
Maximum switching voltage | 440 V AC | Control threshold undervoltage | 300…430 V |
Setting accuracy of the switching threshold | +/-3 % | Switching threshold drift | <= 0.06 % per degree centigrade depending permissible ambient air temperature<br /><= 0.5 % within the measuring range |
Setting accuracy of time delay | 10 P | Time delay drift | <= 0.07 % per degree centigrade depending on the rated operational temperature<br /><= 0.5 % within the measuring range |
Hysteresis | 5 % fixed de-energisation threshold | delay at power up | 650 ms |
Maximum measuring cycle | 80 ms | [Ui] rated insulation voltage | 500 V IEC |
Supply frequency | 50/60 Hz +/- 5 % | Operating position | Any position without derating |
Connections - terminals | Screw terminals, 2 x 1.5 mm²flexible with cable end<br />Screw terminals, 2 x 2.5 mm²flexible without cable end | Tightening torque | 5.3…9.7 lbf.in (0.6…1.1 N.m) |
Mechanical durability | 30000000 cycles | [Ith] conventional free air thermal current | 8 A |
Switching capacity in mA | 10 mA 12 V | Switching voltage | 250 V AC |
Contacts material | 90/10 silver nickel contacts | Number of cables | 2 |
Height | 3.07 in (78 mm) | Width | 0.9 in (22.5 mm) |
Depth | 3.1 in (80 mm) | Terminals description ISO n°1 | ALT<br />(25-26-28)OC<br />(L1-L2-L3)CO<br />(15-16-18)OC |
Output relay state | Tripped, fault present | 9 mm pitches | 2.5 |
Net Weight | 0.24 lb(US) (0.11 kg) | Terminals description ISO n°2 | (L1-L2-L3)CO<br />(11-12-14)OC<br />(21-22-24)OC<br />ALT |
Electromagnetic compatibility | Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2<br />Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2<br />Resistance to electrostatic discharge - test level: 6 kV (contact) conforming to IEC 61000-4-2 level 3<br />Resistance to electrostatic discharge - test level: 8 kV (air) conforming to IEC 61000-4-2 level 3 | Standards | EN/IEC 60255-6 |
Product Certifications | CSA<br />GL<br />UL | marking | CE |
Directives | 73/23/EEC - low voltage directive<br />89/336/EEC - electromagnetic compatibility | Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
Ambient air temperature for operation | -4…149 °F (-20…65 °C) | Relative humidity | 15…85 % 3K3 IEC 60721-3-3 |
Vibration resistance | 0.35 ms 10…55 Hz)IEC 60068-2-6 | Shock resistance | 15 gn 11 ms IEC 60068-2-27 |
IP degree of protection | IP20 IEC 60529 terminals)<br />IP50 IEC 60529 casing) | Pollution degree | 3 IEC 60664-1 |
Overvoltage category | III IEC 60664-1 | Dielectric test voltage | 2.5 kV |
Non-dissipating shock wave | 4.8 kV | Resistance to electrostatic discharge | 6 kV contact IEC 61000-4-2 level 3<br />8 kV air IEC 61000-4-2 level 3 |
Resistance to electromagnetic fields | 9.1 V/m (10 V/m) IEC 61000-4-3 level 3 | Resistance to fast transients | 2 kV IEC 61000-4-4 level 3 |
Disturbance radiated/conducted | CISPR 22 - class A<br />CISPR 11 group 1 - class A |
Specifications may be subject to change without notice