schneider RM4UA32F

Selling Points

  • 1Adjustable Time Delay: Set time delays from 0.05 to 30 seconds to suit your control needs.
  • 2Over/Undervoltage Detection: Monitor and respond to over/undervoltage conditions with precision.
  • 3Robust Construction: Built to withstand millions of operating cycles with high-quality insulation.
  • 4Flexible Measurement Range: Measure voltages from 1 to 100 V AC and 5 to 50 V DC.
  • 5Compact Design: Easy rail mounting and screw fixing for seamless integration into your system.
Product Details
RM4UA32F
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Harmony Relay
Relay Type
Voltage measurement relay
Product or Component Type
Industrial measurement and control relays
Relay name
RM4U
Relay monitored parameters
Overvoltage or undervoltage detection
time delay
Adjustable 0.05...30 s
Contacts type and composition
2 C/O
Maximum switching voltage
440 V AC
operating voltage tolerance
0.85...1.1 Uc
Power consumption in VA
1.9…3.3 VA AC
Output contacts
2 C/O
Hysteresis
5…30 % adjustable voltage threshold setting
Internal input resistance
112000 Ohm<br />23000 Ohm<br />225000 Ohm
Permissible continuous overload
150 V<br />90 V<br />300 V
Permissible non repetitive overload
100 A <= 1 s<br />200 A <= 1 s<br />550 A <= 1 s
Switching threshold drift
<= 0.06 % per degree centigrade depending permissible ambient air temperature<br /><= 0.5 % within the supply voltage range (0.85...1.1 Un)
Setting accuracy of time delay
10 P
Time delay drift
<= 0.07 % per degree centigrade depending on the rated operational temperature<br /><= 0.5 % within the supply voltage range (0.85...1.1 Un)
Quality labels
CE
Setting accuracy of the switching threshold
+/-5 %
Operating position
Any position without derating
Overvoltage category
III IEC 60664-1
[Ui] rated insulation voltage
500 V IEC
Supply disconnection value
> 0.1 Uc
Connections - terminals
Screw terminals, 2 x 1.5 mm²flexible with cable end<br />Screw terminals, 2 x 2.5 mm²flexible without cable end
[Ie] rated operational current
2 A 158 °F (70 °C) 24 V DC-13 IEC 60947-5-1/1991<br />2 A 158 °F (70 °C) 24 V DC-13 VDE 0660<br />3 A 158 °F (70 °C) 115 V AC-15 IEC 60947-5-1/1991<br />3 A 158 °F (70 °C) 115 V AC-15 VDE 0660<br />3 A 158 °F (70 °C) 24 V AC-15 IEC 60947-5-1/1991<br />3 A 158 °F (70 °C) 24 V AC-15 VDE 0660<br />3 A 158 °F (70 °C) 250 V AC-15 IEC 60947-5-1/1991<br />3 A 158 °F (70 °C) 250 V AC-15 VDE 0660<br />0.1 A 158 °F (70 °C) 250 V DC-13 IEC 60947-5-1/1991<br />0.1 A 158 °F (70 °C) 250 V DC-13 VDE 0660<br />0.3 A 158 °F (70 °C) 115 V DC-13 IEC 60947-5-1/1991<br />0.3 A 158 °F (70 °C) 115 V DC-13 VDE 0660
Tightening torque
5.3…9.7 lbf.in (0.6…1.1 N.m)
Mechanical durability
30000000 cycles
[Ith] conventional free air thermal current
8 A
Switching capacity in mA
10 mA 12 V
Contacts material
90/10 silver nickel contacts
Number of cables
2
Width
0.9 in (22.5 mm)
Height
3.07 in (78 mm)
Depth
3.1 in (80 mm)
Terminals description ISO n°1
(15-16-18)OC<br />(25-26-28)OC<br />(A1-A2)CO<br />(C-B1-B2-B3)CO
Output relay state
Tripped if A measured > A set
9 mm pitches
2.5
Net Weight
0.370 lb(US) (0.168 kg)
Electromagnetic compatibility
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2<br />Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Ambient air temperature for operation
-4…149 °F (-20…65 °C)
Vibration resistance
0.35 ms 10…55 Hz)IEC 60068-2-6
Shock resistance
15 gn 11 ms IEC 60068-2-27
Standards
EN/IEC 60255-6
Product Certifications
UL<br />CSA<br />GL
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Relative humidity
15…85 % 3K3 IEC 60721-3-3
IP degree of protection
IP20 IEC 60529 terminals)<br />IP50 IEC 60529 casing)
Pollution degree
3 IEC 60664-1
Directives
89/336/EEC - electromagnetic compatibility<br />73/23/EEC - low voltage directive
Resistance to electrostatic discharge
6 kV contact IEC 61000-4-2 level 3<br />8 kV air IEC 61000-4-2 level 3
Resistance to electromagnetic fields
9.1 V/m (10 V/m) IEC 61000-4-3 level 3
Resistance to fast transients
2 kV IEC 61000-4-4 level 3
Protection against electric shocks
2 kV level 3 IEC 61000-4-5
Disturbance radiated/conducted
CISPR 11 group 1 - class A<br />CISPR 22 - class A
Dielectric test voltage
2.5 kV
Non-dissipating shock wave
4.8 kV

Specifications may be subject to change without notice