schneider RXG22ND

Selling Points

  • 1Designed with 100,000 operating cycles for resistive loads and 10,000,000 mechanical cycles.
  • 2Suitable for both DC and AC applications, with a maximum switching voltage of 250 V AC and 30 V DC.
  • 3Includes a lockable test button and LED indicator for easy status monitoring.
  • 4Meets UL, IEC, and CSA standards for safety and reliability.
  • 5Plug-in relay design for easy installation on DIN rail or panel mounting systems.
Product Details
RXG22ND
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Harmony Relay
Series name
Interface relay
Product or Component Type
Plug-in relay
Device short name
RXG
Contacts type and composition
2 C/O
[Ithe] conventional enclosed thermal current
5 A -40…131 °F (-40…55 °C)
Local signalling
Flag
Status LED
With
[Ie] rated operational current
5 A 30 V DC) UL<br />5 A 30 V DC) IEC<br />5 A 250 V AC) IEC<br />5 A 250 V AC) UL
Electrical durability
100000 cycles NO resistive at 55 °C<br />100000 cycles NC resistive at 55 °C
Coil resistance
6700 Ohm +/- 10 %
Shock resistance
20 gn in operation<br />100 gn not in operation
Mounting position
Any position
[Uc] control circuit voltage
60 V DC
Colour of cover
Standard
Drop-out voltage threshold
>= 0.1 Uc DC
Load current
5 A 250 V AC
Minimum switching capacity
50 mW at 10 mA, 5 V DC
Maximum switching capacity
1250 VA
Control Type
Lockable test button
Torque Value
7.08 lbf.in (0.8 N.m)
Contact resistance
100 mOhm
Insulation resistance
1000 MOhm at 500 V DC
Electrical Insulation Class
Class F
Mechanical durability
10000000 cycles
Safety reliability data
B10d = 100000
Operating time
20 ms
Reset time
20 ms
Overvoltage category
III
Maximum switching voltage
250 V AC<br />30 V DC
Protection category
RT I
Operating rate
<= 1800 cycles/hour under load<br /><= 18000 cycles/hour no-load
Pollution degree
2
Utilisation coefficient
20 %
[Ui] rated insulation voltage
250 V IEC<br />300 V CSA<br />300 V UL
Dielectric strength
1000 V AC between contacts with micro disconnection<br />5000 V AC between coil and contact with reinforced insulation<br />3000 V AC between poles with basic insulation
Test levels
Level A group mounting
Device presentation
Complete product
Contacts material
Silver alloy (AgSnO2In2O3)
Net Weight
0.04 lb(US) (0.02 kg)
Standards
UL 508<br />IEC 61810-1<br />CSA C22.2 No 14
Product Certifications
CE<br />EAC<br />UL<br />CSA
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient Air Temperature for Operation
-40…158 °F (-40…70 °C)
IP Degree of Protection
IP40
Relative humidity
10…85 %
Vibration resistance
3 gn +/- 0.75 mm 10…150 Hz)in operation<br />5 gn +/- 0.75 mm 10…150 Hz)not in operation