ParameterValueParameterValue
Range of Product
Harmony Electromechanical Relays
Series name
Miniature
Product or Component Type
Plug-in relay
Device short name
RXM
Contacts type and composition
4 C/O
[Uc] control circuit voltage
110 V DC
Status LED
With
Control Type
Lockable test button
Utilisation coefficient
20 %
Shape of pin
Flat
[Ui] rated insulation voltage
250 V IEC<br />300 V CSA<br />300 V UL
[Uimp] rated impulse withstand voltage
2.5 kV 1.2/50 µs
Contacts material
AgNi
[Ie] rated operational current
3 A 28 V DC) NC IEC<br />3 A 250 V AC) NC IEC<br />6 A 28 V DC) NO IEC<br />6 A 250 V AC) NO IEC<br />6 A 277 V AC) UL<br />8 A 30 V DC) UL
Continuous output current
5 A
Maximum switching voltage
250 V IEC
resistive rated load
6 A 250 V AC<br />6 A 28 V DC
Maximum switching capacity
1500 VA/168 W
Minimum switching capacity
170 mW 10 mA, 17 V
Operating rate
<= 1200 cycles/hour under load<br /><= 18000 cycles/hour no-load
Mechanical durability
10000000 cycles
Electrical durability
100000 cycles resistive
average coil consumption
0.9 W
Drop-out voltage threshold
>= 0.1 Uc
operate time
20 ms
release time
20 ms
average coil resistance
13440 Ohm 20 °C +/- 10 %
Rated operational voltage limits
88...121 V DC
Safety reliability data
B10d = 100000
Protection category
RT I
Test levels
Level A group mounting
Operating position
Any position
CAD overall height
3.1 in (79 mm)
CAD overall depth
3.09 in (78.45 mm)
Net Weight
0.082 lb(US) (0.037 kg)
Device presentation
Complete product
Dielectric strength
1300 V AC between contacts with micro disconnection<br />2000 V AC between coil and contact with basic insulation<br />2000 V AC between poles with basic insulation
Product Certifications
UL<br />Lloyd's<br />CE<br />CSA<br />GOST<br />IECEE CB Scheme
Standards
CSA C22.2 No 14<br />UL 508<br />IEC 61810-1
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient air temperature for operation
-40…131 °F (-40…55 °C)
Vibration resistance
3 gn +/- 1 mm 10…150 Hz)5 cycles in operation<br />5 gn +/- 1 mm 10…150 Hz)5 cycles not operating
IP degree of protection
IP40 conforming to IEC 60529
Shock resistance
10 gnin operation<br />30 gnnot operating
Pollution degree
2