ParameterValueParameterValue
Range of Product
Harmony Relay
Series name
Miniature
Product or Component Type
Plug-in relay
Device short name
RXM
Contacts type and composition
4 C/O
[Uc] control circuit voltage
24 V DC
[Ithe] conventional enclosed thermal current
6 A -40…131 °F (-40…55 °C)
Status LED
With
Control Type
Lockable test button
Utilisation coefficient
20 %
Shape of pin
Flat
[Ui] rated insulation voltage
250 V IEC<br />300 V CSA<br />300 V UL
[Uimp] rated impulse withstand voltage
2.5 kV 1.2/50 µs
Contacts material
AgNi
[Ie] rated operational current
3 A 28 V DC) NC IEC<br />3 A 250 V AC) NC IEC<br />6 A 28 V DC) NO IEC<br />6 A 250 V AC) NO IEC<br />6 A 277 V AC) UL<br />8 A 30 V DC) UL
Maximum switching voltage
250 V IEC
resistive rated load
6 A 250 V AC<br />6 A 28 V DC
Maximum switching capacity
1500 VA/168 W
Minimum switching capacity
170 mW 10 mA, 17 V
Operating rate
<= 1200 cycles/hour under load<br /><= 18000 cycles/hour no-load
Mechanical durability
10000000 cycles
Electrical durability
100000 cycles resistive
average coil consumption
0.9 W
Drop-out voltage threshold
>= 0.1 Uc
operate time
20 ms
release time
20 ms
average coil resistance
650 Ohm 20 °C +/- 10 %
Rated operational voltage limits
19.2...26.4 V DC
Safety reliability data
B10d = 100000
Protection category
RT I
Operating position
Any position
Net Weight
0.082 lb(US) (0.037 kg)
Device presentation
Complete product
Dielectric strength
1300 V AC between contacts with micro disconnection<br />2000 V AC between coil and contact<br />2000 V AC between poles
Product Certifications
UL<br />CSA<br />GOST<br />CE<br />Lloyd's
Standards
EN/IEC 61810-1<br />CSA C22.2 No 14<br />UL 508
Ambient Air Temperature for Storage
-40…185 °F (-40…85 °C)
Ambient air temperature for operation
-40…131 °F (-40…55 °C)
Vibration resistance
3 gn +/- 1 mm 10…150 Hz)5 cycles in operation<br />5 gn +/- 1 mm 10…150 Hz)5 cycles not operating
IP degree of protection
IP40 conforming to EN/IEC 60529
Shock resistance
10 gnin operation<br />30 gnnot operating
Pollution degree
2