schneider TM3DI8A

Selling Points

  • 1Advanced PLC with high processing power for complex applications.
  • 2Enhanced I/O capabilities with up to 512 digital inputs/outputs.
  • 3Modular design for easy integration and customization.
  • 4Reliable operation in harsh industrial environments.
  • 5Compatible with a wide range of Schneider Electric software tools.
Product Details
TM3DI8A
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM3
Product or Component Type
Discrete input module
Range Compatibility
Modicon M241<br />Modicon M251<br />Modicon M221<br />Modicon M262
Discrete input number
8 input IEC 61131-2 Type 1
Discrete input voltage
120 V
Discrete input current
7.5 mA input
Discrete I/O number
8
Current consumption
0 mA 24 V DC via bus connector at state on)<br />0 mA 24 V DC via bus connector at state off)<br />70 mA 5 V DC via bus connector at state on)<br />25 mA 5 V DC via bus connector at state off)
Discrete input voltage type
AC
Voltage state 1 guaranteed
79...132 V input
Current state 1 guaranteed
2...15 mA input)
Voltage state 0 guaranteed
0...20 V input
Current state 0 guaranteed
<= 15 mA input)
Input impedance
11 kOhm
Response time
25 ms (turn-on)<br />30 ms (turn-off)
Local signalling
for input status 1 LED per channel (green)
Electrical connection
11 x 2.5 mm² removable screw terminal block pitch 5.08 mm for inputs
Insulation
Non-insulated between inputs<br />Between input and internal logic 1500 V AC<br />Between input groups 1500 V AC
Marking
CE
Mounting support
Top hat type TH35-15 rail IEC 60715<br />Top hat type TH35-7.5 rail IEC 60715<br /> plate or panel with fixing kit
Height
3.5 in (90 mm)
Depth
3.3 in (84.6 mm)
Width
1.08 in (27.4 mm)
Standards
IEC 61131-2
Product Certifications
cULus<br />CE<br />UKCA<br />RCM<br />EAC<br />cULus HazLoc
Resistance to electrostatic discharge
8 kV in air IEC 61000-4-2<br />4 kV on contact IEC 61000-4-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3<br />2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3<br />0.9 V/m (1 V/m) 2 GHz...3 GHz IEC 61000-4-3
Resistance to magnetic fields
98.4 A/m (30 A/m) 50/60 Hz IEC 61000-4-8
Resistance to fast transients
1 kV I/OIEC 61000-4-4
Surge withstand
2 kV I/O common mode IEC 61000-4-5 AC
Resistance to conducted disturbances
10 V 0.15...80 MHz IEC 61000-4-6<br />3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission
Radiated emissions 40 dBμV/m QP class A 10 m)30…230 MHz IEC 55011<br />Radiated emissions 47 dBμV/m QP class A 10 m)230…1000 MHz IEC 55011
Ambient Air Temperature for Operation
14…95 °F (-10…35 °C) vertical installation<br />14…131 °F (-10…55 °C) horizontal installation
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
10…95 %, without condensation in operation)<br />10…95 %, without condensation in storage)
IP degree of protection
IP20 with protective cover in place
Pollution degree
2
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
3.5 mm 5…8.4 Hz DIN rail<br />3 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz panel<br />3 gn 8.4…150 Hz panel
Shock resistance
15 gn 11 ms

Specifications may be subject to change without notice