schneider TM3SAC5R

Selling Points

  • 1High Integrity Safety Module: Meets IEC/EN 61508-1:2010 SIL 2 standards for safety integrity.
  • 224 VDC Operation: Compatible with 24 VDC supply voltage, ensuring reliable operation in various industrial settings.
  • 3Compact Design: Dimensions: 1.72 in W x 2.87 in D x 3.7 in H, ideal for space-constrained applications.
  • 4Multiple Outputs: Features three enabling paths and one signaling path for comprehensive monitoring.
  • 5CE and CSA Certified: Compliant with CE and CSA standards, ensuring global regulatory compliance.
Product Details
TM3SAC5R
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM3 Safety
Product or Component Type
Safety module
Device short name
TM3SAC
Safety module application
For emergency stop and switch monitoring
Function of module
Emergency stop monitoring 1-channel wiring<br />Emergency stop monitoring 2-channel wiring<br />Monitoring of a movable guard with 2 switches and automatic start
Safety level
Can reach PL d/category 3 ISO 13849-1 2008<br />Can reach PL d/category 3 ISO 13849-2 2012<br />Can reach SILCL 2 IEC 62061 2005<br />Can reach SIL 2 IEC 61508 2010
Safety reliability data
DC = 95 % ISO 13849-1<br />PFHd = 5E-9 1/h IEC 61508-1 1 operation/hour DC-13 24 V DC, <4 A<br />PFHd = 30E-9 1/h IEC 61508-1 60 operations/hour DC-13 24 V DC, <1 A<br />MTTFd = 500 years ISO 13849-1 1 operation/hour DC-13 24 V DC, <4 A<br />MTTFd = 85 years ISO 13849-1 60 operations/hour DC-13 24 V DC, <1 A<br />SFF = 95 % IEC 61508-1<br />HFT = 1 IEC 61508-1<br />Type = A IEC 61508-1
Synchronisation time between inputs
Unlimited
Connections - terminals
Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² flexible without cable end 13-14, 23-24, 33-34<br />Captive screw clamp terminals, removable terminal block 1 x 0.2...1 x 2.5 mm² solid without cable end 13-14, 23-24, 33-34<br />Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, with bezel 13-14, 23-24, 33-34<br />Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 2.5 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34<br />Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² flexible without cable end 13-14, 23-24, 33-34<br />Captive screw clamp terminals, removable terminal block 2 x 0.2...2 x 1.5 mm² solid without cable end 13-14, 23-24, 33-34<br />Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 1 mm² flexible with cable end, without bezel 13-14, 23-24, 33-34<br />Captive screw clamp terminals, removable terminal block 2 x 0.5...2 x 1.5 mm² flexible with cable end, with double bezel 13-14, 23-24, 33-34<br />Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² flexible without cable end other terminals<br />Captive screw clamp terminals, removable terminal block 1 x 0.14...1 x 1.5 mm² solid without cable end other terminals<br />Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 0.5 mm² flexible with cable end, with bezel other terminals<br />Captive screw clamp terminals, removable terminal block 1 x 0.25...1 x 1.5 mm² flexible with cable end, without bezel other terminals<br />Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.5 mm² flexible without cable end other terminals<br />Captive screw clamp terminals, removable terminal block 2 x 0.14...2 x 0.75 mm² solid without cable end other terminals<br />Captive screw clamp terminals, removable terminal block 2 x 0.25...2 x 0.34 mm² flexible with cable end, without bezel other terminals<br />Captive screw clamp terminals, removable terminal block 2 x 0.5 mm² flexible with cable end, with double bezel other terminals
Output type
Relay instantaneous opening, 3 NO, potential free
Number of safety circuits
3 NO relay instantaneous opening
Maximum switching voltage
230 V AC-15 50 Hz relay instantaneous opening)<br />24 V DC-13 relay instantaneous opening)
[Us] rated supply voltage
24 V - 15...20 % DC
Power consumption in W
0.2 W 5 V DC<br />3.6 W 24 V DC
Input protection type
Internal, electronic
[Uc] control circuit voltage
24 V DC
Maximum cable distance between devices
98.4 ft (30 m)
Breaking capacity
4 A 24 V 50 ms DC-13 relay output
Output thermal current
6 A per relay relay output
[Ith] conventional free air thermal current
18 A
Associated fuse rating
4 A gG or gL relay output IEC 60947-5-1<br />6 A fast blow relay output IEC 60947-5-1
Minimum output current
10 mA relay output
Output voltage
10 V relay output
Maximum response time on input open
40 ms
[Ui] rated insulation voltage
300 V 2)IEC 60647-5-1
[Uimp] rated impulse withstand voltage
4 kV III IEC 60647-5-1
Current consumption
100 mA 24 V DC external supply at state on)
Local signalling
for user 6 LEDs (green/red)
Electrical Connection
Screw terminal
Standards
EN 1088/ISO 14119<br />ISO 13850<br />IEC 60947-1<br />IEC 60204-1<br />IEC 60947-5-1
Product Certifications
TÜV<br />CSA 61010-2-201 (pending)<br />CSA Haz Loc Class 1 Division 2 (pending)<br />RCM<br />ANSI Haz Loc Class 1 Division 2 (pending)<br />EAC<br />UL 61010-2-201
Marking
EFUP 10<br />RCM<br />CSA<br />UL<br />TÜV<br />CE<br />EAC
Electromagnetic compatibility
Electrostatic discharge immunity test - test level: 8 kV (air discharge) conforming to IEC 61000-4-2<br />Electrostatic discharge immunity test - test level: 6 kV (contact discharge) conforming to IEC 61000-4-2<br />Susceptibility to electromagnetic fields - test level: 10 V/m (80 MHz to 1 GHz) conforming to IEC 61000-4-3<br />Susceptibility to electromagnetic fields - test level: 3 V/m (1.4 GHz...2 GHz) conforming to IEC 61000-4-3<br />Susceptibility to electromagnetic fields - test level: 1 V/m (2 GHz...3 GHz) conforming to IEC 61000-4-3<br />Magnetic field at power frequency - test level: 30 A/m (50...60 Hz) conforming to IEC 61000-4-8<br />Electrical fast transient/burst immunity test - test level: 3 kV (power lines (DC)) conforming to IEC 61000-4-4<br />Electrical fast transient/burst immunity test - test level: 2 kV (I/O) conforming to IEC 61000-4-4<br />1.2/50 µs shock waves immunity test - test level: 1 kV (power lines (DC)) conforming to IEC 61000-4-5<br />Conducted RF disturbances - test level: 10 V (0.15...80 MHz) conforming to IEC 61000-4-6<br />Radiated emission - test level: 40 dBµV/m class A (24 V) conforming to IEC 55011<br />Radiated emission - test level: 47 dBµV/m class A (24 V) conforming to IEC 55011
Mounting support
Top hat type TH35-7.5 rail IEC 60715<br />Top hat type TH35-15 rail IEC 60715<br /> wall mount using attached fasteners
Height
3.7 in (94 mm)
Depth
2.9 in (73 mm)
Width
1.7 in (43.7 mm)
Net Weight
0.42 lb(US) (0.19 kg)
Resistance to electrostatic discharge
8 kV in air IEC 61000-4-2<br />6 kV on contact IEC 61000-4-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3<br />2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3<br />0.9 V/m (1 V/m) 2 GHz...3 GHz IEC 61000-4-3
Resistance to magnetic fields
98.4 A/m (30 A/m) 50/60 Hz IEC 61000-4-8
Resistance to fast transients
3 kV power lines (DC) DC)IEC 61000-4-4<br />2 kV I/O linesIEC 61000-4-4
Surge withstand
1 kV power lines (DC) differential mode IEC 61000-4-5 DC<br />1 kV power lines (DC) common mode IEC 61000-4-5 DC
Resistance to conducted disturbances
10 V 0.15...80 MHz IEC 61000-4-6
Electromagnetic emission
Radiated emissions 50 dBµV/m class A 24 V DC)30…230 Hz IEC 61131-3<br />Radiated emissions 57 dBµV/m class A 24 V DC)230…1000 Hz IEC 61131-3
Ambient Air Temperature for Operation
14…131 °F (-10…55 °C) horizontal installation
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
10…95 %, without condensation in operation)<br />10…95 %, without condensation in storage)
IP degree of protection
IP20 terminals)IEC 60529
Pollution degree
2
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
+/- 3.5 mm 5…150 Hz)IEC 60068-2-6
Shock resistance
15 gn 11 ms IEC 60068-2-27
Mechanical robustness
Bumps 6 ms 300 shocks 25 gn) IEC 60068-2-27

Specifications may be subject to change without notice