schneider TM3TI8T

Selling Points

  • 1High-Resolution Analog Input: Features 8 analog input channels with 16-bit resolution for precise temperature measurements.
  • 2Versatile Compatibility: Compatible with Modicon M221, M241, and M251 logic controllers for seamless integration.
  • 3Wide Temperature Range: Supports thermocouples from -200°C to 1300°C, ensuring broad application flexibility.
  • 4Robust Design: Built with screw terminal blocks and designed for DIN rail mounting, ensuring secure and efficient installation.
  • 5Enhanced Safety Features: Meets CE, UKCA, RCM, EAC, and cULus certifications for reliable operation in various industrial environments.
Product Details
TM3TI8T
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM3
Product or Component Type
Analog input module
Range Compatibility
Modicon M221<br />Modicon M241<br />Modicon M251<br />Modicon M262
Analogue input number
8
Analogue input type
thermocouple - 200...1000 °C thermocouple J<br /> thermocouple - 200...1300 °C thermocouple K<br /> thermocouple 0...1760 °C thermocouple R<br /> thermocouple 0...1760 °C thermocouple S<br /> thermocouple 0...1820 °C thermocouple B<br /> thermocouple - 200...400 °C thermocouple T<br /> thermocouple - 200...1300 °C thermocouple N<br /> thermocouple - 200...800 °C thermocouple E<br /> thermocouple 0...2315 °C thermocouple C<br />NTC 10k thermistor -90...150 °C<br />PTC thermistor 100...10000 Ohm<br /> thermocouple - 200...1000 °C
Analogue input resolution
16 bits<br />15 bits + sign
Input impedance
>= 1 MOhm thermocouple<br />>= 1 MOhm temperature probe<br />>= 1 MOhm thermistor
LSB value
0.1 °C thermocouple<br />0.1 °C NTC<br />1 Ohm PTC/NTC
Conversion time
100 ms + 100 ms per channel + 1 controller cycle time
Sampling duration
100 ms
Absolute accuracy error
+/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple C 0...2315 °C<br />+/- 6 °C at 77 °F (25 °C) for thermocouple R, S 0...200 °C<br />+/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple R, S 200...1760 °C<br />+/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple B 300...1820 °C<br />+/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple K - 200...0 °C<br />+/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple K 0...1300 °C<br />+/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple J - 200...0 °C<br />+/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple J 0...1000 °C<br />+/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple E - 200...0 °C<br />+/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple E 0...800 °C<br />+/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple T - 200...0 °C<br />+/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple T 0...400 °C<br />+/- 0.4 % of full scale at 77 °F (25 °C) for thermocouple N - 200...0 °C<br />+/- 0.2 % of full scale at 77 °F (25 °C) for thermocouple N 0...1300 °C
Temperature Drift
+/- 0.01 %FS/°C
Repeat accuracy
+/-0.5 %FS
Non-linearity
+/- 0.2 %FS
Cross talk
<= 1 LSB
[Us] rated supply voltage
24 V DC
Supply voltage limits
20.4…28.8 V
Type of cable
Twisted shielded pairs cable <98.4 ft (30 m) input
Current consumption
30 mA 24 V DC via external supply<br />45 mA 5 V DC via bus connector<br />40 mA 5 V DC via bus connector
Local signalling
for PWR 1 LED (green)
Electrical connection
10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs and supply<br />10 x 1.5 mm² removable screw terminal block pitch 3.81 mm for inputs
Insulation
Between input and supply 1500 V AC<br />Between input and internal logic 500 V AC
Marking
CE
Surge withstand
1 kV power supply common mode IEC 61000-4-5<br />0.5 kV power supply differential mode IEC 61000-4-5<br />1 kV input common mode IEC 61000-4-5
Mounting support
Top hat type TH35-15 rail IEC 60715<br />Top hat type TH35-7.5 rail IEC 60715<br /> plate or panel with fixing kit
Height
3.5 in (90 mm)
Depth
2.8 in (70 mm)
Width
0.9 in (23.6 mm)
Net Weight
0.24 lb(US) (0.11 kg)
Standards
IEC 61131-2
Product Certifications
CE<br />UKCA<br />RCM<br />EAC<br />cULus<br />cULus HazLoc
Resistance to electrostatic discharge
8 kV in air IEC 61000-4-2<br />4 kV on contact IEC 61000-4-2
Resistance to electromagnetic fields
9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3<br />2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3<br />0.9 V/m (1 V/m) 2 GHz...3 GHz IEC 61000-4-3
Resistance to magnetic fields
98.4 A/m (30 A/m) IEC 61000-4-8
Resistance to fast transients
1 kV IEC 61000-4-4 I/O)
Resistance to conducted disturbances
10 V 0.15...80 MHz IEC 61000-4-6<br />3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission
Radiated emissions 40 dBμV/m QP class A 10 m)30…230 MHz IEC 55011<br />Radiated emissions 47 dBμV/m QP class A 10 m)230…1000 MHz IEC 55011
Immunity to microbreaks
10 ms
Ambient Air Temperature for Operation
14…131 °F (-10…55 °C) horizontal installation<br />14…95 °F (-10…35 °C) vertical installation
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
10…95 %, without condensation in operation)<br />10…95 %, without condensation in storage)
IP Degree of Protection
IP20
Pollution degree
2
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
3.5 mm 5…8.4 Hz DIN rail<br />3 gn 8.4…150 Hz DIN rail
Shock resistance
15 gn 11 ms

Specifications may be subject to change without notice