schneider TM5SAI2H

Selling Points

  • 115-bit resolution for precise analog input.
  • 2Compatible with +/-10V and 0-20mA inputs.
  • 3Designed for Modicon TM5 systems, suitable for industrial control applications.
  • 4Built with durable components, ensuring reliable operation in harsh environments.
  • 5Meets CSA C22.2 No 142, IEC 61131-2, and UL 508 standards for safety and performance.
Product Details
TM5SAI2H
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Analog input module
Analogue input number
2
Analogue input type
current 0...20 mA differential<br /> voltage +/- 10 V differential
Analogue input resolution
15 bits + sign +/- 10 V<br />15 bits 0...20 mA
Range Compatibility
Modicon LMC058<br />Modicon M258
Product Compatibility
Logic controller<br />Motion controller
Measurement resolution
305 µV, +/- 10 V<br />610 nA, 0...20 mA
Color
White
Input impedance
>= 20 mOhm voltage
Load impedance ohmic
<= 400 Ohm current)
Sampling duration
50 µs
Measurement error
< 0.08 % of full scale +/- 10 V +/- 10 V 25 °C<br />< 0.08 % of full scale 0...20 mA 0...20 mA 25 °C
Temperature coefficient
0.01 %FS/°C
Non-linearity
< 0.01 %FS voltage<br />< 0.015 %FS current
Type of Cable
Shielded cable
Isolation
500 Vrms AC insulation between channel and bus<br />No insulation between channels
Supply
Internal
[Us] rated supply voltage
24 V DC -15...20 %
Common mode rejection
> 70 dB
Local signalling
1 LED green power supply<br />1 LED red power supply<br />2 LEDs green input status
Current consumption
2 mA 5 V DC bus<br />50 mA 24 V DC input/output
Maximum power dissipation in W
1.21 W
marking
CE
Net Weight
0.055 lb(US) (0.025 kg)
Standards
CSA C22.2 No 142<br />IEC 61131-2<br />UL 508<br />CSA C22.2 No 213
Product Certifications
C-tick<br />GOST-R<br />cULus<br />CSA
Ambient air temperature for operation
32…131 °F (0…55 °C) without derating horizontal installation)<br />32…140 °F (0…60 °C) with derating factor horizontal installation)<br />32…122 °F (0…50 °C) vertical installation)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Resistance to electrostatic discharge
4 kV on contact IEC 61000-4-2<br />8 kV in air IEC 61000-4-2
Resistance to electromagnetic fields
0.9 V/m (1 V/m) 2...2.7 GHz IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz IEC 61000-4-3
Resistance to fast transients
1 kV IEC 61000-4-4 I/O)<br />1 kV IEC 61000-4-4 shielded cable)<br />2 kV IEC 61000-4-4 power lines)
Surge withstand
0.5 kV differential mode IEC 61000-4-5<br />1 kV common mode IEC 61000-4-5
Electromagnetic compatibility
EN/IEC 61000-4-6
Disturbance radiated/conducted
CISPR 11

Specifications may be subject to change without notice