Product Model
TM5SDI20DFS

Selling Points
- 1The TM5SDI20DFS features 20 safety-related digital inputs for secure and reliable data collection.
- 2Operates at 24V DC, ensuring compatibility with various automation systems.
- 3Software-configurable input filters for precise signal management and error detection.
- 4Meets SIL 3 standards for safety integrity, ensuring high reliability in critical applications.
- 5Includes short-circuit and overload protection, along with 500Vrms AC insulation between channels for enhanced safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon TM5 | Product or Component Type | Safety dc discrete input module |
Discrete input number | 20 | Discrete input voltage | 24 V |
Range Compatibility | PacDrive LMC motion controller | Product Compatibility | PacDrive LMC Pro<br />PacDrive LMC Pro 2<br />PacDrive LMC Eco |
Discrete input voltage type | DC | input voltage limits | 20.4...28.8 V |
Discrete input logic | Sink | Discrete input current | 2.48 mA |
input impedance | 9.68 kOhm | Color | Red |
Voltage state 0 guaranteed | <= 5 V | Voltage state 1 guaranteed | >= 15 V |
Input filtering | <= 500 ms configurable by software<br /><= 150 ms hardware | Protection Type | Short-circuit protection<br />Overload protection |
Isolation | No insulation between channels<br />500 Vrms AC insulation between channel and bus | Maximum voltage drop | <2 V DC |
Maximum supply current for sensors | 200 mA | Maximum power consumption in W | 1.6 W internal<br />0.4 W bus |
Local signalling | 1 LED green power supply<br />1 LED red power supply<br />2 LEDs red safety status<br />20 LEDs green/red input status | Electrical connection | 2 wires |
marking | CE | Safety level | SIL 3 IEC 61508<br />SIL 3 IEC 62061<br />PL = e EN 13849-1 |
Safety reliability data | PFD < 1E-5<br />MTTFd = 2500 years<br />PFH < 1E-10 | Net Weight | 0.130 lb(US) (0.059 kg) |
Standards | CSA C22.2 No 142<br />UL 508<br />EN 13849-1<br />IEC 61131-2<br />IEC 61508<br />IEC 62061 | Product Certifications | cULus<br />CSA |
Ambient air temperature for operation | 32…122 °F (0…50 °C) vertical installation)<br />32…131 °F (0…55 °C) horizontal installation) | Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
Relative Humidity | 5…95 % without condensation | IP degree of protection | IP20IEC 60529 |
Pollution degree | 2 IEC 60664 | Operating altitude | 0...6561.68 ft (0...2000 m) |
Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) | Vibration resistance | 1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail |
Shock resistance | 15 gn 11 ms | Electromagnetic compatibility | Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5<br />Conducted RF disturbances IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11 |
Specifications may be subject to change without notice