Product Model

TM5SDI20DFS

In Stock
Last updated: 2025/4/23
schneider TM5SDI20DFS

Selling Points

  • 1The TM5SDI20DFS features 20 safety-related digital inputs for secure and reliable data collection.
  • 2Operates at 24V DC, ensuring compatibility with various automation systems.
  • 3Software-configurable input filters for precise signal management and error detection.
  • 4Meets SIL 3 standards for safety integrity, ensuring high reliability in critical applications.
  • 5Includes short-circuit and overload protection, along with 500Vrms AC insulation between channels for enhanced safety.
Product Details
TM5SDI20DFS
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Safety dc discrete input module
Discrete input number
20
Discrete input voltage
24 V
Range Compatibility
PacDrive LMC motion controller
Product Compatibility
PacDrive LMC Pro<br />PacDrive LMC Pro 2<br />PacDrive LMC Eco
Discrete input voltage type
DC
input voltage limits
20.4...28.8 V
Discrete input logic
Sink
Discrete input current
2.48 mA
input impedance
9.68 kOhm
Color
Red
Voltage state 0 guaranteed
<= 5 V
Voltage state 1 guaranteed
>= 15 V
Input filtering
<= 500 ms configurable by software<br /><= 150 ms hardware
Protection Type
Short-circuit protection<br />Overload protection
Isolation
No insulation between channels<br />500 Vrms AC insulation between channel and bus
Maximum voltage drop
<2 V DC
Maximum supply current for sensors
200 mA
Maximum power consumption in W
1.6 W internal<br />0.4 W bus
Local signalling
1 LED green power supply<br />1 LED red power supply<br />2 LEDs red safety status<br />20 LEDs green/red input status
Electrical connection
2 wires
marking
CE
Safety level
SIL 3 IEC 61508<br />SIL 3 IEC 62061<br />PL = e EN 13849-1
Safety reliability data
PFD < 1E-5<br />MTTFd = 2500 years<br />PFH < 1E-10
Net Weight
0.130 lb(US) (0.059 kg)
Standards
CSA C22.2 No 142<br />UL 508<br />EN 13849-1<br />IEC 61131-2<br />IEC 61508<br />IEC 62061
Product Certifications
cULus<br />CSA
Ambient air temperature for operation
32…122 °F (0…50 °C) vertical installation)<br />32…131 °F (0…55 °C) horizontal installation)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative Humidity
5…95 % without condensation
IP degree of protection
IP20IEC 60529
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5<br />Conducted RF disturbances IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11

Specifications may be subject to change without notice