schneider TM5SDI2A

Selling Points

  • 1High-Quality Component: Designed for industrial applications with long-term reliability.
  • 2Dual Input Channels: Supports two digital input channels for versatile connectivity.
  • 3Wide Voltage Range: Compatible with 100-240V AC, ensuring broad operational flexibility.
  • 4Robust Safety Features: Includes hardware and software input filters, short circuit protection, and isolation.
  • 5Compact Design: Weighs only 25 grams, making it easy to integrate into various systems.
Product Details
TM5SDI2A
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Discrete input module
Discrete input number
2
Discrete input voltage
100...240 V
Range Compatibility
Modicon LMC058<br />PacDrive LMC motion controller<br />Modicon M258
Product Compatibility
PacDrive LMC Pro<br />Motion controller<br />PacDrive LMC Pro 2<br />Logic controller<br />PacDrive LMC Eco
Discrete input voltage type
AC
input voltage limits
100...240 V
Discrete input current
5…11 mA
Color
Black
Input filtering
<= 25 ms configurable by software<br /><= 30 ms hardware from state 1 to state 0<br /><= 40 ms hardware from state 0 to state 1
Protection Type
Short-circuit protection
Isolation
No insulation between channels<br />2500 V AC insulation between channel and bus for 1 minute
Maximum voltage drop
<2 V at 500 mA sensor supply
Maximum supply current for sensors
500 mA
Current consumption
28 mA 5 V DC bus
Maximum power dissipation in W
0.69 W
Local signalling
1 LED green power supply<br />1 LED red power supply<br />2 LEDs green input status
Electrical connection
3 wires
marking
CE
Net Weight
0.055 lb(US) (0.025 kg)
Standards
UL 508<br />CSA C22.2 No 142<br />CSA C22.2 No 213<br />IEC 61131-2
Product Certifications
GOST-R<br />CSA<br />C-tick<br />cULus
Ambient air temperature for operation
14…131 °F (-10…55 °C) without derating horizontal installation)<br />14…140 °F (-10…60 °C) with derating factor horizontal installation)<br />14…122 °F (-10…50 °C) vertical installation)
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Relative Humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact EN/IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air EN/IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz EN/IEC 61000-4-3<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz EN/IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O EN/IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable EN/IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines EN/IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode EN/IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode EN/IEC 61000-4-5<br />Conducted RF disturbances EN/IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11

Specifications may be subject to change without notice