Product Model
TM5SDI2DFS

Selling Points
- 12 Safety-Related Digital Inputs: Ensure reliable safety operations with two dedicated digital input channels.
- 2Configurable Input Filters: Customize input filters via software for precise signal management.
- 32 Pulse Outputs: Utilize two test (pulse) outputs for comprehensive system testing and validation.
- 424 VDC Rated Voltage: Operate at 24 VDC, suitable for various industrial control systems.
- 5Compliance with Safety Standards: Meets stringent safety standards including EN ISO 13849 (PL e), IEC 61508 (SIL 3), and IEC 62061 (SIL 3).
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon TM5 | Product or Component Type | Safety dc discrete input module |
Discrete input number | 2 | Discrete input voltage | 24 V |
Range Compatibility | Modicon M258<br />Modicon LMC058<br />PacDrive LMC motion controller | Product Compatibility | Motion controller<br />PacDrive LMC Pro 2<br />Logic controller<br />PacDrive LMC Pro<br />PacDrive LMC Eco |
Discrete input voltage type | DC | input voltage limits | 20.4...28.8 V |
Discrete input logic | Sink | Discrete input current | 3.45 mA |
input impedance | 7 kOhm | Color | Red |
Voltage state 0 guaranteed | <= 5 V | Voltage state 1 guaranteed | >= 15 V |
Input filtering | <= 500 ms configurable by software<br /><= 150 ms hardware | Protection Type | Short-circuit protection<br />Overload protection |
Isolation | 500 Vrms AC insulation between channel and bus<br />No insulation between channels | Maximum voltage drop | <0.6 V at 100 mA |
Maximum supply current for sensors | 300 mA | Maximum power consumption in W | 1 W internal<br />0.25 W bus |
Local signalling | 1 LED green power supply<br />1 LED red power supply<br />2 LEDs green/red input status<br />2 LEDs red safety status | Electrical connection | 2 wires |
marking | CE | Safety level | SIL 3 IEC 61508<br />SIL 3 IEC 62061<br />PL = e EN 13849-1 |
Safety reliability data | MTTFd > 100 years<br />PFD < 1E-5<br />PFH < 1E-9 | Net Weight | 0.055 lb(US) (0.025 kg) |
Standards | CSA C22.2 No 142<br />EN 13849-1<br />IEC 62061<br />UL 508<br />IEC 61131-2<br />IEC 61508 | Product Certifications | CSA<br />cULus<br />GOST-R |
Ambient air temperature for operation | 14…122 °F (-10…50 °C) vertical installation)<br />14…131 °F (-10…55 °C) horizontal installation)<br />14…140 °F (-10…60 °C) | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) |
Relative Humidity | 5…95 % without condensation | IP degree of protection | IP20IEC 60529 |
Pollution degree | 2 IEC 60664 | Operating altitude | 0...6561.68 ft (0...2000 m) |
Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) | Vibration resistance | 1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail |
Shock resistance | 15 gn 11 ms | Electromagnetic compatibility | Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5<br />Conducted RF disturbances IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11 |
Specifications may be subject to change without notice