Product Model
TM5SDO2TFS

Selling Points
- 1Compliant with SIL 3 Standards: Meets IEC 61508 and IEC 62061 standards for safety-related applications.
- 2High Reliability: Offers a Mean Time To Failure (MTTFd) of over 100 years and a Probability of Failure on Demand (PFD) of less than 1E-5.
- 3Integrated Protection: Includes thermal switch-off for over-current or short-circuit protection and integrated protection for switching inductive loads.
- 4Compact Design: IP20-rated, compact design suitable for distributed and remote I/O architectures.
- 5Versatile Compatibility: Compatible with PacDrive LMC motion controllers and other Modicon TM5 systems.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon TM5 | Product or Component Type | Safety dc discrete output module |
Discrete output number | 2 | Discrete output type | Solid state |
Range Compatibility | PacDrive LMC motion controller | Product Compatibility | PacDrive LMC Pro 2<br />PacDrive LMC Pro<br />PacDrive LMC Eco |
Output voltage | 24 V DC | Output voltage limits | 20.4...28.8 V |
Discrete output logic | Source | Current per channel | 0.5 A |
Maximum current per output common | 1 A | Color | Red |
Peak output current | 12 A | Switching frequency | <= 500 Hz resistive |
[Ures] residual voltage | 120 mV without OSSD | Maximum leakage current | 10 µA when switched off |
Protection Type | Short-circuit protection<br />Overload protection | Isolation | 500 Vrms AC insulation between channel and bus<br />No insulation between channels |
Maximum power consumption in W | 0.25 W bus<br />0.98 W internal | Local signalling | 1 LED green power supply<br />1 LED red power supply<br />2 LEDs red safety status<br />2 LEDs red/orange output status |
Electrical connection | 2 wires | marking | CE |
Safety level | SIL 3 IEC 61508<br />SIL 3 IEC 62061<br />PL = e EN 13849-1 | Safety reliability data | MTTFd > 100 years<br />PFD < 1E-5<br />PFH < 1E-9 |
Net Weight | 0.055 lb(US) (0.025 kg) | Standards | CSA C22.2 No 142<br />EN 13849-1<br />IEC 61508<br />IEC 62061<br />UL 508<br />IEC 61131-2 |
Product Certifications | CSA<br />GOST-R<br />cULus | Ambient air temperature for operation | 14…122 °F (-10…50 °C) vertical installation)<br />14…131 °F (-10…55 °C) horizontal installation) |
Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) | Relative Humidity | 5…95 % without condensation |
IP degree of protection | IP20IEC 60529 | Pollution degree | 2 IEC 60664 |
Operating altitude | 0...6561.68 ft (0...2000 m) | Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) |
Vibration resistance | 1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz | Shock resistance | 15 gn 11 ms |
Electromagnetic compatibility | Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 1 kV I/O IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 2 kV power lines IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV differential mode IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV common mode IEC 61000-4-5<br />Conducted RF disturbances IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11 |
Specifications may be subject to change without notice