Product Model
TM5SE1IC02505

Selling Points
- 1High-Performance Counter Module: Designed for Modicon TM5 systems with 1 HSC incremental input.
- 2250 kHz Frequency: Supports high-speed counting applications.
- 316/32 Bits Resolution: Offers precise counter input resolution.
- 4Dual Power Supply: Compatible with 5 Vdc or 24 Vdc encoder supply.
- 5IP20 Protection: Meets safety standards with IP20 protection rating.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon TM5 | Product or Component Type | Counter module |
Function of module | 2 x 24 V DC RS422 sink auxiliary inputs<br />24 V DC encoder power supply | Discrete input number | 1 |
Counting frequency | 250 kHz | Encoder type | 1 incremental encoder |
Range Compatibility | Modicon LMC058<br />Modicon M258 | Product Compatibility | Motion controller<br />Logic controller |
Counter inputs resolution | 16 bits/32 bits | Maximum cycle time | 2 ms |
Input compatibility | 1 incremental encoder (5 V) | Isolation | 500 Vrms AC insulation between channel and bus |
Discrete input logic | Sink | Discrete input voltage | 24 V DC |
Discrete input current | 3.3 mA 24 V | Input resistance | 7.19 kOhm |
Input filtering | <= 200 ms | Current consumption | 2 mA 5 V DC bus<br />63 mA 24 V DC input/output |
Maximum power dissipation in W | 1.51 W | marking | CE |
Standards | UL 508<br />CSA C22.2 No 142<br />CSA C22.2 No 213<br />IEC 61131-2 | Product Certifications | cULus<br />C-tick<br />GOST-R<br />CSA |
Ambient air temperature for operation | 32…131 °F (0…55 °C) without derating horizontal installation)<br />32…140 °F (0…60 °C) with derating factor horizontal installation)<br />32…122 °F (0…50 °C) vertical installation) | Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
Relative humidity | 5…95 % without condensation | IP degree of protection | IP20IEC 61131-2 |
Pollution degree | 2 IEC 60664 | Operating altitude | 0...6561.68 ft (0...2000 m) |
Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) | Vibration resistance | 1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail |
Shock resistance | 15 gn 11 ms | Resistance to electrostatic discharge | 4 kV on contact IEC 61000-4-2<br />8 kV in air IEC 61000-4-2 |
Resistance to electromagnetic fields | 0.9 V/m (1 V/m) 2...2.7 GHz IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz IEC 61000-4-3 | Resistance to fast transients | 1 kV IEC 61000-4-4 I/O)<br />1 kV IEC 61000-4-4 shielded cable)<br />2 kV IEC 61000-4-4 power lines) |
Surge withstand | 0.5 kV differential mode IEC 61000-4-5<br />1 kV common mode IEC 61000-4-5 | Electromagnetic compatibility | EN/IEC 61000-4-6 |
Disturbance radiated/conducted | CISPR 11 |
Specifications may be subject to change without notice