Product Model

TM5SE1IC20005

In Stock
Last updated: 2025/4/23
schneider TM5SE1IC20005

Selling Points

  • 1High-speed counter module with 1 HSC incremental encoder at 4 MHz.
  • 2Compatible with PacDrive LMC Eco, LMC Pro, and LMC Pro2 motion controllers.
  • 3Offers 16/32 bits counter inputs resolution for precise measurement.
  • 4Supports up to 2 ms maximum cycle time for efficient processing.
  • 5Features 500 Vrms AC insulation between channel and bus for enhanced safety.
Product Details
TM5SE1IC20005
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Counter module
Function of module
2 x 24 V DC RS422 sink auxiliary inputs<br />24 V DC encoder power supply
Discrete input number
2
Counting frequency
4 MHz
Encoder type
1 incremental encoder
Range Compatibility
PacDrive LMC Eco<br />PacDrive LMC Pro<br />PacDrive LMC Pro2
Product Compatibility
Motion controller
Counter inputs resolution
16 bits/32 bits
Maximum cycle time
2 ms
Isolation
500 Vrms AC insulation between channel and bus
Discrete input logic
Sink
Discrete input voltage
24 V DC
Discrete input current
24 V
Input filtering
<= 200 ms
Current consumption
2 mA 5 V DC bus<br />63 mA 24 V DC input/output
Maximum power dissipation in W
1.51 W
marking
CE
Net Weight
0.055 lb(US) (0.025 kg)
Standards
UL 508<br />CSA C22.2 No 142<br />CSA C22.2 No 213<br />IEC 61131-2
Product Certifications
cULus<br />C-tick<br />GOST-R<br />CSA
Ambient air temperature for operation
32…131 °F (0…55 °C) without derating horizontal installation)<br />32…140 °F (0…60 °C) with derating factor horizontal installation)<br />32…122 °F (0…50 °C) vertical installation)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Resistance to electrostatic discharge
4 kV on contact EN/IEC 61000-4-2<br />8 kV in air EN/IEC 61000-4-2
Resistance to electromagnetic fields
0.9 V/m (1 V/m) 2...2.7 GHz EN/IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz EN/IEC 61000-4-3
Resistance to fast transients
1 kV EN/IEC 61000-4-4 I/O)<br />1 kV EN/IEC 61000-4-4 shielded cable)<br />2 kV EN/IEC 61000-4-4 power lines)
Surge withstand
0.5 kV differential mode EN/IEC 61000-4-5<br />1 kV common mode EN/IEC 61000-4-5
Electromagnetic compatibility
EN/IEC 61000-4-6
Disturbance radiated/conducted
CISPR 11