Product Model
TM5SE1IC20005

Selling Points
- 1High-speed counter module with 1 HSC incremental encoder at 4 MHz.
- 2Compatible with PacDrive LMC Eco, LMC Pro, and LMC Pro2 motion controllers.
- 3Offers 16/32 bits counter inputs resolution for precise measurement.
- 4Supports up to 2 ms maximum cycle time for efficient processing.
- 5Features 500 Vrms AC insulation between channel and bus for enhanced safety.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon TM5 | Product or Component Type | Counter module |
Function of module | 2 x 24 V DC RS422 sink auxiliary inputs<br />24 V DC encoder power supply | Discrete input number | 2 |
Counting frequency | 4 MHz | Encoder type | 1 incremental encoder |
Range Compatibility | PacDrive LMC Eco<br />PacDrive LMC Pro<br />PacDrive LMC Pro2 | Product Compatibility | Motion controller |
Counter inputs resolution | 16 bits/32 bits | Maximum cycle time | 2 ms |
Isolation | 500 Vrms AC insulation between channel and bus | Discrete input logic | Sink |
Discrete input voltage | 24 V DC | Discrete input current | 24 V |
Input filtering | <= 200 ms | Current consumption | 2 mA 5 V DC bus<br />63 mA 24 V DC input/output |
Maximum power dissipation in W | 1.51 W | marking | CE |
Net Weight | 0.055 lb(US) (0.025 kg) | Standards | UL 508<br />CSA C22.2 No 142<br />CSA C22.2 No 213<br />IEC 61131-2 |
Product Certifications | cULus<br />C-tick<br />GOST-R<br />CSA | Ambient air temperature for operation | 32…131 °F (0…55 °C) without derating horizontal installation)<br />32…140 °F (0…60 °C) with derating factor horizontal installation)<br />32…122 °F (0…50 °C) vertical installation) |
Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) | Relative humidity | 5…95 % without condensation |
IP degree of protection | IP20IEC 61131-2 | Pollution degree | 2 IEC 60664 |
Operating altitude | 0...6561.68 ft (0...2000 m) | Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) |
Vibration resistance | 1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail | Shock resistance | 15 gn 11 ms |
Resistance to electrostatic discharge | 4 kV on contact EN/IEC 61000-4-2<br />8 kV in air EN/IEC 61000-4-2 | Resistance to electromagnetic fields | 0.9 V/m (1 V/m) 2...2.7 GHz EN/IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz EN/IEC 61000-4-3 |
Resistance to fast transients | 1 kV EN/IEC 61000-4-4 I/O)<br />1 kV EN/IEC 61000-4-4 shielded cable)<br />2 kV EN/IEC 61000-4-4 power lines) | Surge withstand | 0.5 kV differential mode EN/IEC 61000-4-5<br />1 kV common mode EN/IEC 61000-4-5 |
Electromagnetic compatibility | EN/IEC 61000-4-6 | Disturbance radiated/conducted | CISPR 11 |
Specifications may be subject to change without notice