schneider TM5SEAISG

Selling Points

  • 1High Resolution: 24-bit resolution for precise measurements.
  • 2Wide Compatibility: Compatible with full-bridge strain gauges from 85 to 5000 Ohms.
  • 3Flexible Configuration: Scalable configurations for remote/distributed IO islands.
  • 4Robust Design: 500 Vrms AC insulation between channel and bus, ensuring reliability.
  • 5Easy Integration: Compatible with logic and motion controllers, simplifying system setup.
Product Details
TM5SEAISG
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Analog input module
Analogue input number
1
Analogue input type
full-bridge strain gauge 85...5000 Ohm differential
Analogue input resolution
24 bits
Range Compatibility
Modicon M258<br />Modicon LMC058
Product Compatibility
Logic controller<br />Motion controller
Maximum number of sensors
4
Color
White
Type of Cable
Shielded cable
Isolation
No insulation between channels<br />500 Vrms AC insulation between channel and bus
Supply
Internal
[Us] rated supply voltage
24 V DC
Local signalling
1 LED green power supply<br />1 LED red power supply<br />1 LED green input status
Current consumption
2 mA 5 V DC bus<br />52 mA 24 V DC input/output<br />65 mA 5.5 V DC full-bridge (4/6 wires)
Maximum power dissipation in W
1.25 W
marking
CE
Net Weight
0.055 lb(US) (0.025 kg)
Temperature Drift
10 ppm/°C
Standards
IEC 61131-2<br />CSA C22.2 No 142<br />CSA C22.2 No 213<br />UL 508
Product Certifications
cULus<br />GOST-R<br />CSA<br />C-tick
Ambient air temperature for operation
32…131 °F (0…55 °C) without derating horizontal installation)<br />32…140 °F (0…60 °C) with derating factor horizontal installation)<br />32…122 °F (0…50 °C) vertical installation)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Resistance to electrostatic discharge
4 kV on contact IEC 61000-4-2<br />8 kV in air IEC 61000-4-2
Resistance to electromagnetic fields
0.9 V/m (1 V/m) 2...2.7 GHz IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz IEC 61000-4-3
Resistance to fast transients
1 kV IEC 61000-4-4 I/O)<br />1 kV IEC 61000-4-4 shielded cable)<br />2 kV IEC 61000-4-4 power lines)
Surge withstand
0.5 kV differential mode IEC 61000-4-5<br />1 kV common mode IEC 61000-4-5
Electromagnetic compatibility
EN/IEC 61000-4-6
Disturbance radiated/conducted
CISPR 11

Specifications may be subject to change without notice