Product Model

TM5SPDD12F

In Stock
Last updated: 2025/4/23
schneider TM5SPDD12F

Selling Points

  • 1Flexible I/O Configuration: Scalable and configurable for various industrial applications.
  • 2High-Current Protection: Equipped with a 6.3 A internal fuse for short-circuit protection.
  • 3Compact Design: Lightweight at 0.055 lb (0.025 kg) for easy installation on DIN rails.
  • 4Environmental Compliance: Meets EU RoHS and WEEE standards, ensuring eco-friendly disposal.
  • 5Reliable Performance: Operates within a wide ambient air temperature range (32°F to 122°F).
Product Details
TM5SPDD12F
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Common distribution module
Product Specific Application
Cabling various voltage to power 12 I/O in 24 V DC
Range Compatibility
Modicon LMC058<br />Modicon M258
Product Compatibility
Motion controller<br />Logic controller
[Us] rated supply voltage
24 V
Network type
DC
Short-circuit protection
6.3 A internal fuse
marking
CE
Net Weight
0.055 lb(US) (0.025 kg)
Standards
UL 508<br />CSA C22.2 No 213<br />IEC 61131-2<br />CSA C22.2 No 142
Product Certifications
C-tick<br />GOST-R<br />cULus<br />CSA
Ambient air temperature for operation
32…122 °F (0…50 °C) vertical installation)<br />32…131 °F (0…55 °C) without derating horizontal installation)<br />32…140 °F (0…60 °C) with derating factor horizontal installation)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Resistance to electrostatic discharge
4 kV on contact IEC 61000-4-2<br />8 kV in air IEC 61000-4-2
Resistance to electromagnetic fields
0.9 V/m (1 V/m) 2...2.7 GHz IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz IEC 61000-4-3
Resistance to fast transients
1 kV IEC 61000-4-4 I/O)<br />1 kV IEC 61000-4-4 shielded cable)<br />2 kV IEC 61000-4-4 power lines)
Surge withstand
0.5 kV differential mode IEC 61000-4-5<br />1 kV common mode IEC 61000-4-5
Electromagnetic compatibility
EN/IEC 61000-4-6
Disturbance radiated/conducted
CISPR 11

Specifications may be subject to change without notice