ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Power distribution module
Product Specific Application
Cabling various voltage to power 6 I/O in 0 V DC & 6 I/O in 24 V DC
Range Compatibility
Modicon LMC058<br />Modicon M258
Product Compatibility
Motion controller<br />Logic controller
[Us] rated supply voltage
24 V
Network type
DC
Short-circuit protection
6.3 A internal fuse
marking
CE
Net Weight
0.055 lb(US) (0.025 kg)
Standards
UL 508<br />IEC 61131-2<br />CSA C22.2 No 213<br />CSA C22.2 No 142
Product Certifications
GOST-R<br />C-tick<br />CSA<br />cULus
Ambient air temperature for operation
32…122 °F (0…50 °C) vertical installation)<br />32…131 °F (0…55 °C) without derating horizontal installation)<br />32…140 °F (0…60 °C) with derating factor horizontal installation)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Resistance to electrostatic discharge
4 kV on contact IEC 61000-4-2<br />8 kV in air IEC 61000-4-2
Resistance to electromagnetic fields
0.9 V/m (1 V/m) 2...2.7 GHz IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz IEC 61000-4-3
Resistance to fast transients
1 kV IEC 61000-4-4 I/O)<br />1 kV IEC 61000-4-4 shielded cable)<br />2 kV IEC 61000-4-4 power lines)
Surge withstand
0.5 kV differential mode IEC 61000-4-5<br />1 kV common mode IEC 61000-4-5
Electromagnetic compatibility
EN/IEC 61000-4-6
Disturbance radiated/conducted
CISPR 11