  • 1Redundant Safety Inputs: 2 redundant safety-related analog inputs for thermocouples and PT100/PT1000 temperature compensation.
  • 2High Resolution: 24-bit digital converter resolution for precise temperature measurements.
  • 3Configurable Filtering: Configurable input filter and switching threshold for customizable signal processing.
  • 4Wide Temperature Range: Compatible with various thermocouple types (J, K, N, S, R, C, T) and PT100/PT1000 sensors.
  • 5Comprehensive Safety Features: Meets SIL 3, Cat. 4, PL e standards with 500 Vrms AC insulation between channels and bus.
Product Details
TM5STI4ATCFS
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM5
Product or Component Type
Analog input module
Analogue input number
4
Analogue input type
thermocouple - 210...1200 °C thermocouple J<br /> thermocouple - 270...1300 °C thermocouple N<br /> thermocouple - 270...1372 °C thermocouple K<br /> thermocouple - 50...1768 °C thermocouple S<br /> thermocouple - 50...1768 °C thermocouple R<br /> thermocouple 0...2320 °C thermocouple C<br /> thermocouple -270...+400 °C thermocouple T
Analogue input resolution
24 bits
Range Compatibility
Modicon M258<br />Modicon LMC058
Product Compatibility
Logic controller<br />Motion controller
Measurement resolution
0.1 °C
Color
Red
Input filtering
1 ms configurable by software<br />2 ms configurable by software<br />10 ms configurable by software<br />16.7 ms configurable by software<br />20 ms configurable by software<br />33.3 ms configurable by software<br />40 ms configurable by software<br />66.7 ms configurable by software
Sampling duration
5 ms<br />7 ms<br />14 ms<br />20 ms<br />25 ms<br />40 ms<br />48 ms<br />62 ms
Measurement error
2.5 % of full scale - 210...1200 °C thermocouple J 25 °C<br />2.9 % of full scale - 270...1372 °C thermocouple K<br />3.3 % of full scale - 270...1300 °C thermocouple N<br />8.3 % of full scale - 50...1768 °C thermocouple S<br />7.4 % of full scale - 50...1768 °C thermocouple R<br />4.8 % of full scale 0...2320 °C thermocouple C<br />4.6 % of full scale - 270...400 °C thermocouple T<br />1.6 % of full scale - 40...130 °C Pt 100/Pt 1000
Temperature coefficient
< 0.0021 %FS/°C thermocouple
Type of Cable
Shielded cable
Isolation
500 Vrms AC insulation between channel and bus<br />No insulation between channels
Supply
Internal
[Us] rated supply voltage
24 V DC -15...20 %
Common mode rejection
> 70 dB
Local signalling
1 LED green power supply<br />1 LED red power supply<br />6 LEDs green input status
Current consumption
2 mA 5 V DC bus<br />30 mA 24 V DC input/output
Maximum power dissipation in W
0.73 W
marking
CE
Net Weight
0.146 lb(US) (0.066 kg)
Standards
EN 50156-1<br />IEC 62061<br />IEC 61508<br />ISO 13849-1<br />UL 508<br />IEC 61511
Product Certifications
cULus<br />CSA
Ambient air temperature for operation
32…104 °F (0…40 °C) vertical installation)<br />32…131 °F (0…55 °C) horizontal installation)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative humidity
5…95 % without condensation
IP degree of protection
IP20IEC 61131-2
Pollution degree
2 IEC 60664
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
1 gn 8.4…150 Hz DIN rail<br />3.5 mm 5…8.4 Hz DIN rail
Shock resistance
15 gn 11 ms
Resistance to electrostatic discharge
4 kV on contact IEC 61000-4-2<br />8 kV in air IEC 61000-4-2
Resistance to electromagnetic fields
0.9 V/m (1 V/m) 2...2.7 GHz IEC 61000-4-3<br />9.1 V/m (10 V/m) 80...2000 MHz IEC 61000-4-3
Resistance to fast transients
1 kV IEC 61000-4-4 I/O)<br />1 kV IEC 61000-4-4 shielded cable)<br />2 kV IEC 61000-4-4 power lines)
Surge withstand
0.5 kV differential mode IEC 61000-4-5<br />1 kV common mode IEC 61000-4-5
Electromagnetic compatibility
EN/IEC 61000-4-6
Disturbance radiated/conducted
CISPR 11

Specifications may be subject to change without notice