schneider TM7BDI8B

Selling Points

  • 1Built with plastic for durability and resistance to harsh environments.
  • 2Compatible with Modicon LMC058 and M258 controllers via the TM5 expansion bus.
  • 3Equipped with overload, short-circuit, and reverse polarity protection.
  • 4Simple screw terminal connections for quick setup.
  • 5Meets IP67 standards for protection against dust and moisture.
Product Details
TM7BDI8B
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon TM7
Product or Component Type
Discrete I/O expansion block
Range Compatibility
Modicon LMC058<br />Modicon M258
Enclosure Material
Plastic
Bus type
TM7 bus
[Ue] rated operational voltage
24 V DC
Input/output number
8
input/output number of block
8 I
Discrete input number
8
Discrete input voltage
24 V
Discrete input voltage type
DC
Discrete input current
7 mA
Discrete input logic
Positive
Sensor power supply
24 V, 500 mA for all channels overload, short-circuit and reverse polarity protection
Electrical connection
1 male connector M12 - B coding - 4 ways bus IN<br />1 female connector M12 - B coding - 4 ways bus OUT<br />1 male connector M8 - 4 ways power IN<br />1 female connector M8 - 4 ways power OUT<br />8 female connectors M8 - 3 ways sensor
Local signalling
for bus diagnostic 2 LEDs<br /> for sensor power supply diagnostics 2 LEDs
Operating position
Any position
Fixing Mode
By 2 screws
Net Weight
0.40 lb(US) (0.18 kg)
Standards
IEC 61131-2
Product Certifications
C-tick<br />ATEX II 3g EEx nA II T5<br />cURus<br />GOST-R
marking
CE
Ambient Air Temperature for Operation
14…140 °F (-10…60 °C)
Ambient Air Temperature for Storage
-13…185 °F (-25…85 °C)
Relative humidity
5…95 % without condensation or dripping water
Pollution degree
2 IEC 60664
IP degree of protection
IP67 conforming to IEC 61131-2
Operating altitude
0...6561.68 ft (0...2000 m)
Storage altitude
0.0000000000…9842.5 ft (0…3000 m)
Vibration resistance
7.5 mm constant amplitude 2…8 Hz)IEC 60721-3-5 Class 5M3<br />2 gn constant acceleration 8…200 Hz)IEC 60721-3-5 Class 5M3<br />4 gn constant acceleration 200…500 Hz)IEC 60721-3-5 Class 5M3
Shock resistance
30 gn 11 ms IEC 60721-3-5 Class 5M3
Electromagnetic compatibility
Electrostatic discharge immunity test, 4 kV on contact IEC 61000-4-2<br />Electrostatic discharge immunity test, 8 kV in air IEC 61000-4-2<br />Susceptibility to electromagnetic fields, 1 V/m 2...2.7 GHz IEC 61000-4-3<br />Susceptibility to electromagnetic fields, 10 V/m 80...2000 MHz IEC 61000-4-3<br />Electrical fast transient/burst immunity test, 2 kV power supply IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV input/output IEC 61000-4-4<br />Electrical fast transient/burst immunity test, 1 kV shielded cable IEC 61000-4-4<br />1.2/50 µs shock waves immunity test, 0.5 kV power supply (common mode) IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV power supply (differential mode) IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 0.5 kV unshielded links (common mode) IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV unshielded links (differential mode) IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 0.5 kV shielded links (common mode) IEC 61000-4-5<br />1.2/50 µs shock waves immunity test, 1 kV shielded links (differential mode) IEC 61000-4-5<br />Conducted RF disturbances IEC 61000-4-6<br />Conducted and radiated emissions CISPR 11

Specifications may be subject to change without notice