Product Model
TMSCO1

Selling Points
- 1Integrated IIoT Connectivity: Seamlessly integrates with Modicon M262 logic/motion controllers for enhanced IIoT connectivity.
- 2CANopen Protocol Support: Features one CANopen master access with support for up to 63 slaves, ensuring efficient device communication.
- 3Compact Design: Measures 30mm width, 88mm depth, and 100mm height, making it perfect for space-constrained industrial settings.
- 4Robust Environmental Compliance: Compliant with various standards including UL 61010-1/-2-201, CSA C22.2 No. 61010-1/-2-201, and EN 61131-2.
- 5Advanced Safety Features: Equipped with 4 kV contact and 8 kV air resistance to electrostatic discharge, ensuring reliable operation in harsh environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon M262 | Product or Component Type | Smart communication module |
Range Compatibility | Modicon M262 | Current consumption | 50 mA 24 V |
Number of module per PLC | 1 maximum per logic controller<br />1 maximum per motion controller | Services | Maximum 63 slave nodes |
communication port protocol | CANopen | Local signalling | for PWR 1 LED (green)<br /> for MOD STS 1 LED (green/red)<br /> for CAN RUN 1 LED (green)<br /> for CAN ERR 1 LED (red) |
Mounting support | Top hat type TH35-15 rail IEC 60715<br />Top hat type TH35-7.5 rail IEC 60715<br /> plate or panel with fixing kit | Width | 1.2 in (30 mm) |
Height | 3.9 in (100 mm) | Depth | 3.5 in (88.3 mm) |
Standards | UL 61010-1<br />UL 61010-2-201<br />CSA C22.2 No 61010-1<br />CSA C22.2 No 61010-2-201<br />CSA C22.2 No 213<br />ANSI/ISA 12-12-01<br />IEC 61131-2 | Product Certifications | CE<br />cULus<br />RCM<br />EAC (pending)<br />Achilles |
Resistance to electrostatic discharge | 4 kV on contact IEC 61000-4-2<br />8 kV on air IEC 61000-4-2 | Resistance to electromagnetic fields | 9.1 V/m (10 V/m) 80 MHz...1 GHz IEC 61000-4-3<br />2.7 V/m (3 V/m) 1.4 GHz...2 GHz IEC 61000-4-3<br />0.9 V/m (1 V/m) 2 GHz...3 GHz IEC 61000-4-3 |
Resistance to fast transients | 2 kV IEC 61000-4-4 power lines)<br />1 kV IEC 61000-4-4 Ethernet line)<br />1 kV IEC 61000-4-4 serial link)<br />1 kV IEC 61000-4-4 input)<br />1 kV IEC 61000-4-4 transistor output) | Resistance to conducted disturbances | 10 V 0.15...80 MHz IEC 61000-4-4<br />3 V 0.1...80 MHz Marine specification (LR, ABS, DNV, GL)<br />10 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) Marine specification (LR, ABS, DNV, GL) |
Electromagnetic emission | Conducted emissions 120...69 dBµV/m QP power lines)10…150 kHz IEC 55011<br />Conducted emissions 63 dBμV/m QP power lines)1.5…30 MHz IEC 55011<br />Radiated emissions 40 dBµV/m A30…230 kHz IEC 55011<br />Conducted emissions 79...63 dBμV/m QP power lines)150…1500 kHz IEC 55011<br />Radiated emissions 47 dBµV/m A230…1000 MHz IEC 55011 | Ambient Air Temperature for Operation | -4…140 °F (-20…60 °C) horizontal installation<br />-4…122 °F (-20…50 °C) vertical installation |
Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) | Relative humidity | 10…95 %, without condensation in operation)<br />10…95 %, without condensation in storage) |
IP degree of protection | IP20 | Pollution degree | 2 |
Operating altitude | 0...6561.68 ft (0...2000 m) | Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) |
Vibration resistance | 3.5 mm 2…8.4 Hz symmetrical rail<br />1 gn 8.4…200 Hz symmetrical rail<br />3.5 mm 2…8.4 Hz panel mounting<br />1 gn 8.4…200 Hz panel mounting | Shock resistance | 15 gn 11 ms |
Specifications may be subject to change without notice