Selling Points

  • 1High-level input signals support for current (4-20 mA, 0-20 mA) and voltage (±10V, 0-10V, 0-5V, 1-5V) inputs.
  • 212-bit analog-to-digital conversion ensures high-resolution and accurate measurement.
  • 3Fast read cycle time of 3 ms + 3 ms per channel, enabling quick data acquisition.
  • 41000Vrms isolation between channels and ground for enhanced safety and signal integrity.
  • 5Compact design with a standard module format, suitable for various industrial applications.
Product Details
TSXAEY800
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Premium Automation platform
Product or Component Type
Analog input module
Input level
High level
Analogue input number
8
Analogue input type
Current 0...20 mA<br />Current 4...20 mA<br />Voltage +/- 10 V<br />Voltage 0...10 V<br />Voltage 0...5 V<br />Voltage 1...5 V
Analog/digital conversion
12 bits
Nominal read cycle time
27 ms
Fast read cycle time
3 ms + 3 ms x number of channels used
Measurement error
0.15 % of full scale 0...5 V 25 °C<br />0.15 % of full scale 1...5 V 25 °C<br />0.19 % of full scale +/- 10 V 25 °C<br />0.19 % of full scale 0...10 V 25 °C<br />0.22 % of full scale +/- 10 V 0...60 °C<br />0.22 % of full scale 0...10 V 0...60 °C<br />0.22 % of full scale 0...5 V 0...60 °C<br />0.22 % of full scale 1...5 V 0...60 °C<br />0.25 % of full scale 0...20 mA 25 °C<br />0.25 % of full scale 4...20 mA 25 °C<br />0.41 % of full scale 0...20 mA 0...60 °C<br />0.41 % of full scale 4...20 mA 0...60 °C
Isolation between channels and bus
1000 Vrms
Isolation between channels and ground
1000 Vrms
Isolation between channels
Common point
Common mode between channels
None
Input overvoltage protection
-15…15 V at state 0 250 Ohm<br />-30…30 V at state 1 250 Ohm
Electrical connection
1 connector SUB-D 25
Overcurrent
-30…30 mA at state 1 250 kOhm
marking
CE
Current consumption
270 mA 5 V DC
Module format
Standard
Net Weight
0.68 lb(US) (0.31 kg)
Standards
IEC 1131
Product Certifications
DNV<br />RINA<br />GL<br />BV<br />LR<br />RMRS<br />ABS
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative Humidity
10…95 % without condensation for operation<br />5…95 % without condensation for storage
Operating altitude
0...6561.68 ft (0...2000 m)
Protective treatment
TC
IP Degree of Protection
IP20
Pollution degree
2