Product Model

TSXDEY16A2

In Stock
Last updated: 2025/4/22
schneider TSXDEY16A2

Selling Points

  • 116 Resistive Isolated Inputs: The TSXDEY16A2 features 16 resistive isolated inputs, ensuring reliable and precise signal detection.
  • 224V DC Negative Logic: Compatible with 24V DC negative logic, this module is ideal for various industrial automation applications.
  • 3Fast Response Time: With a response time of 15 ms, the TSXDEY16A2 ensures quick and accurate data processing.
  • 4CE Marking and Compliance: Meets CE standards and complies with EN/IEC 61131-2 type 2, ensuring safety and reliability.
  • 5Standard Module Format: Available in a standard module format with screw terminal connections for easy integration into your system.
Product Details
TSXDEY16A2
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Premium Automation platform
Product or Component Type
Discrete input module
Discrete input number
16 resistive isolated EN/IEC 61131-2 type 2<br />16 resistive isolated
Discrete input voltage
24 V DC negative<br />24 V AC
Network frequency
50/60 Hz 47…63 Hz AC
Sensor power supply
19…30 V DC<br />20…26 V AC
Input compatibility
With 2-wire/3-wire proximity sensors EN/IEC 60947-5-2
Discrete input current
15 mA AC<br />16 mA DC
Voltage state 1 guaranteed
<= 10 V DC<br />10 V AC
Current state 1 guaranteed
>= 6.5 mA DC<br />6 mA AC
Voltage state 0 guaranteed
>= 19 V DC<br />5 V AC
Current state 0 guaranteed
<= 2 mA DC<br />4 mA AC
Input impedance
1600 Ohm at state 1
Response Time
15 ms<br /><= 20 ms
isalotion resistance
< 10 MOhm 500 V DC
Power dissipation
(1 W + 0.4 W x No of channels used) DC<br />0.89 W AC
Electrical Connection
Screw terminal
marking
CE
Current consumption
80 mA 5 V DC
Module format
Standard
Net Weight
0.68 lb(US) (0.31 kg)
Dielectric strength
1500 V AC 50/60 Hz
Standards
CSA C22.2 No 213 Class I Division 2 Group B<br />93/68/EEC<br />CSA C22.2 No 142<br />73/23/EEC<br />EN/IEC 61131-2<br />IEC 60664<br />89/336/EEC<br />UL 508<br />CSA C22.2 No 213 Class I Division 2 Group D<br />92/31/EEC<br />CSA C22.2 No 213 Class I Division 2 Group A<br />CSA C22.2 No 213 Class I Division 2 Group C
Product Certifications
RINA<br />DNV<br />BV<br />LR<br />GL<br />RMRS<br />ABS
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative Humidity
10…95 % without condensation for operation<br />5…95 % without condensation for storage
Operating altitude
0...6561.68 ft (0...2000 m)
Protective treatment
TC
IP Degree of Protection
IP20
Pollution degree
2

Specifications may be subject to change without notice