Product Model
TSXDSY08R4D

Selling Points
- 1High efficiency up to 95% for reduced energy costs.
- 2Compact design with low noise operation for quiet environments.
- 3Wide input voltage range (100-240V) for global compatibility.
- 4Built-in protection features including overcurrent and overvoltage protection.
- 5Meets or exceeds IEC/EN 60950-1 safety standards for reliability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Premium Automation platform | Product or Component Type | Discrete output module |
Discrete output number | 8 | Discrete output type | Relay protected |
Discrete output voltage | 24...120 V DC EN/IEC 61131-2 19...143 V | [Ith] conventional free air thermal current | 5 A |
Response time | < 10 ms (activation)<br />< 15 ms (deactivation) | Contacts type and composition | 2 x 2 C/O + 2 x 2 NO |
Output overvoltage protection | RC circuit and Ge-Mov | Output overload protection | 6.3 A, interchangeable fuse per common fast blow |
Short-circuit protection | 6.3 A, interchangeable fuse per common fast blow | isalotion resistance | > 10 MOhm 500 V |
Power dissipation | (0.25 W + 0.24 W x No of outputs at state 1) | Electrical durability | 1000000 cycles DC-12 100 W 48 V resistive<br />1000000 cycles DC-12 220 W 100...120 V resistive<br />1000000 cycles DC-12 50 W 24 V resistive<br />1000000 cycles DC-3 100 W 48 V inductive<br />1000000 cycles DC-3 220 W 100...120 V inductive<br />1000000 cycles DC-3 50 W 24 V inductive<br />2000000 cycles DC-3 110 W 100...120 V inductive<br />2000000 cycles DC-3 20 W 24 V inductive<br />2000000 cycles DC-3 50 W 48 V inductive<br />300000 cycles DC-12 100 W 24 V resistive<br />300000 cycles DC-12 200 W 48 V resistive<br />300000 cycles DC-12 440 W 100...120 V resistive |
marking | CE | Electrical connection | Screw terminal block |
Current consumption | 55 mA 5 V DC<br />80 mA 24 V DC rack | Module format | Standard |
Net Weight | 0.82 lb(US) (0.37 kg) | Dielectric strength | 2000 V 50/60 Hz 60 s |
Standards | 89/336/EEC<br />UL 508<br />CSA C22.2 No 213 Class I Division 2 Group C<br />92/31/EEC<br />CSA C22.2 No 213 Class I Division 2 Group B<br />73/23/EEC<br />CSA C22.2 No 213 Class I Division 2 Group D<br />CSA C22.2 No 142<br />93/68/EEC<br />IEC 61131-2<br />CSA C22.2 No 213 Class I Division 2 Group A | Product Certifications | LR<br />GL<br />DNV<br />RINA<br />BV<br />ABS<br />RMRS |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
Relative Humidity | 10…95 % without condensation for operation<br />5…95 % without condensation for storage | Operating altitude | 0...6561.68 ft (0...2000 m) |
Protective treatment | TC | IP Degree of Protection | IP20 |
Pollution degree | 2 |
Specifications may be subject to change without notice