Product Model

TSXDSY16R5

In Stock
Last updated: 2025/4/21
schneider TSXDSY16R5

Selling Points

  • 1High-capacity power supply with 16A output.
  • 2Compact design for easy integration into systems.
  • 3Enhanced reliability with robust construction.
  • 4Wide input voltage range for flexible use.
  • 5Compliant with international safety standards.
Product Details
TSXDSY16R5
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Premium Automation platform
Product or Component Type
Discrete output module
Discrete output number
16
Discrete output type
Relay not protected
Discrete output voltage
12...24 V DC EN/IEC 61131-2 10...34 V<br />24...240 V AC EN/IEC 61131-2 20...264 V
[Ith] conventional free air thermal current
3 A
Response time
< 10 ms (deactivation)<br />< 8 ms (activation)
Contacts type and composition
1 NO
Output overvoltage protection
DC inductive, by discharge diode on each preactuator<br />AC inductive, by RC circuit MOV (ZNO) on each preactuator
Output overload protection
1 external fuse per channel or group of channel fast blow
Short-circuit protection
1 external fuse per channel or group of channel fast blow
isalotion resistance
> 10 MOhm 500 V
Power dissipation
(0.25 W + 0.2 W x No of outputs at state 1)
Electrical durability
1000000 cycles DC-12 24 W 24 V resistive<br />1000000 cycles DC-3 24 W 24 V inductive<br />2000000 cycles DC-3 10 W 24 V inductive<br />300000 cycles DC-12 40 W 24 V resistive<br />100000 cycles AC-14 220 VA 220 V inductive<br />100000 cycles AC-15 220 VA 220 V inductive<br />1000000 cycles AC-12 110 VA 110 V resistive<br />1000000 cycles AC-12 220 VA 220 V resistive<br />1000000 cycles AC-12 50 VA 48 V resistive<br />1000000 cycles AC-14 110 VA 220 V inductive<br />1000000 cycles AC-15 110 VA 220 V inductive<br />150000 cycles AC-14 110 VA 110 V inductive<br />150000 cycles AC-15 110 VA 110 V inductive<br />1500000 cycles AC-14 50 VA 110 V inductive<br />1500000 cycles AC-15 50 VA 110 V inductive<br />2000000 cycles AC-14 24 VA 48 V inductive<br />2000000 cycles AC-15 24 VA 48 V inductive<br />3000000 cycles AC-14 50 VA 220 V inductive<br />3000000 cycles AC-15 50 VA 220 V inductive<br />500000 cycles AC-12 110 VA 48 V resistive<br />500000 cycles AC-12 220 VA 110 V resistive<br />500000 cycles AC-14 24 VA 24 V inductive<br />500000 cycles AC-15 24 VA 24 V inductive<br />5000000 cycles AC-14 10 VA 110 V inductive<br />5000000 cycles AC-14 10 VA 220 V inductive<br />5000000 cycles AC-14 10 VA 48 V inductive<br />5000000 cycles AC-15 10 VA 110 V inductive<br />5000000 cycles AC-15 10 VA 220 V inductive<br />5000000 cycles AC-15 10 VA 48 V inductive<br />700000 cycles AC-12 50 VA 24 V resistive
marking
CE
Electrical connection
Screw terminal block
Current consumption
135 mA 24 V DC rack<br />80 mA 5 V DC
Module format
Standard
Net Weight
0.84 lb(US) (0.38 kg)
Dielectric strength
2000 V 50/60 Hz 60 s
Standards
73/23/EEC<br />IEC 61131-2<br />UL 508<br />CSA C22.2 No 213 Class I Division 2 Group B<br />92/31/EEC<br />89/336/EEC<br />CSA C22.2 No 213 Class I Division 2 Group C<br />CSA C22.2 No 213 Class I Division 2 Group A<br />CSA C22.2 No 142<br />CSA C22.2 No 213 Class I Division 2 Group D<br />93/68/EEC
Product Certifications
BV<br />RINA<br />LR<br />ABS<br />RMRS<br />GL<br />DNV
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative Humidity
10…95 % without condensation for operation<br />5…95 % without condensation for storage
Operating altitude
0...6561.68 ft (0...2000 m)
Protective treatment
TC
IP Degree of Protection
IP20
Pollution degree
2

Specifications may be subject to change without notice