Product Model

TSXDSY16T2

In Stock
Last updated: 2025/4/21
schneider TSXDSY16T2

Selling Points

  • 1High-power output with 16A current capacity.
  • 2Compact design for space-saving installations.
  • 3Wide input voltage range for versatile use.
  • 4Enhanced reliability with robust construction.
  • 5Compliant with international safety standards.
Product Details
TSXDSY16T2
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Premium Automation platform
Product or Component Type
Discrete output module
Discrete output number
16
Discrete output type
Solid state protected
Discrete output voltage
24 V DC positive EN/IEC 61131-2 19...30 V
Discrete output current
0.5 A
Current per channel
0.625 A
Maximum current per module
7 A
Maximum leakage current
0.5 mA at state 0
[Ures] residual voltage
1.2 V
Response time
1.2 ms
Switching frequency
0.5/LI² Hz
Output overvoltage protection
By transil diode
Reverse polarity protection
Reverse mounted diode
Output overload protection
Electronic tripping on reactivation
Short-circuit protection
Electronic tripping on reactivation
Preactuator voltage detection threshold
16 V
Minimum load impedance
48 W
isalotion resistance
> 10 MOhm 500 V
Power dissipation
(1.1 W + 0.75 W x No of outputs x current per module)
marking
CE
Electrical connection
Screw terminal block
Current consumption
80 mA 5 V DC
Module format
Standard
Net Weight
0.75 lb(US) (0.34 kg)
Dielectric strength
1500 V 50/60 Hz 60 s
Standards
CSA C22.2 No 213 Class I Division 2 Group C<br />CSA C22.2 No 142<br />93/68/EEC<br />CSA C22.2 No 213 Class I Division 2 Group D<br />89/336/EEC<br />CSA C22.2 No 213 Class I Division 2 Group A<br />UL 508<br />IEC 61131-2<br />CSA C22.2 No 213 Class I Division 2 Group B<br />73/23/EEC<br />92/31/EEC
Product Certifications
DNV<br />RMRS<br />GL<br />BV<br />ABS<br />RINA<br />LR
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative Humidity
10…95 % without condensation for operation<br />5…95 % without condensation for storage
Operating altitude
0...6561.68 ft (0...2000 m)
Protective treatment
TC
IP Degree of Protection
IP20
Pollution degree
2

Specifications may be subject to change without notice