Product Model

TSXP575634M

In Stock
Last updated: 2025/4/20
schneider TSXP575634M

Selling Points

  • 1Advanced Industrial Automation Solution: Designed for various industrial applications, including manufacturing and energy.
  • 2Robust Design and Performance: Provides reliable and efficient control of motor and lighting systems.
  • 3High Capacity I/O: Supports up to 2040 discrete I/O and 512 analog I/O.
  • 4Versatile Connectivity: Equipped with non-isolated serial link (RS485), Ethernet TCP/IP, and USB ports.
  • 5Comprehensive Warranty: Backed by a 2-year warranty from Schneider Electric for peace of mind.
Product Details
TSXP575634M
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Modicon Premium Automation platform
Product or Component Type
Unity processor
Software Designation
Unity Pro
Concept
Transparent Ready
Number of racks
16 4/6/8 slots<br />8 12 slots
Number of slots
64<br />128<br />96
Discrete I/O processor capacity
2040 I/O
Analogue I/O processor capacity
512 I/O
Number of application specific channel
64
Number of process control channel
30 up to 90 simple loops
Integrated connection type
Non isolated serial link female mini DIN RS485)19.2 kbit/s)<br />Ethernet TCP/IP RJ45<br />USB port12 Mbit/s)
Port Ethernet
10BASE-T/100BASE-TX
Communication module processor capacity
1<br />3<br />8<br />5
Memory description
Internal RAM (with PCMCIA card) 1024 kB data<br />Internal RAM (with PCMCIA card) 7168 kB program<br />Internal RAM (without PCMCIA card) 1024 kB program and data<br />PCMCIA card 16384 kB additional data storage
Maximum size of object areas
128 %MWi internal words located internal data<br />32768 %Mi located internal bits<br />64 %KWi constant words located internal data<br />Unlimited (DFB and EFB function blocks) unlocated internal data<br />Unlimited (elementary and derived data) unlocated internal data
Application structure
1 master task<br />128 event tasks<br />32 timers<br />1 fast task<br />4 auxiliary tasks
Execution time per instruction
0.0375...0.045 µs Boolean with PCMCIA card<br />0.0375...0.045 µs Boolean without PCMCIA card<br />0.045...0.06 µs word or fixed-point arithmetic with PCMCIA card<br />0.045...0.06 µs word or fixed-point arithmetic without PCMCIA card<br />0.48...0.56 µs floating points with PCMCIA card<br />0.48...0.56 µs floating points without PCMCIA card
Number of instructions per ms
14 Kinst/ms 65 % Boolean + 35 % fixed arithmetic with PCMCIA card<br />14 Kinst/ms 65 % Boolean + 35 % fixed arithmetic without PCMCIA card<br />20.26 Kinst/ms 100 % Boolean with PCMCIA card<br />20.26 Kinst/ms 100 % Boolean without PCMCIA card
System overhead
0.07 ms fast task<br />1 ms master task
marking
CE
Local signalling
for Ethernet TCP/IP port ready (RUN) 1 LED (green)<br /> for processor running (RUN) 1 LED (green)<br /> for collision detection (COL) 1 LED (red)<br /> for Ethernet TCP/IP port fault (ERR) 1 LED (red)<br /> for I/O module or configuration fault (I/O) 1 LED (red)<br /> for processor or system fault (ERR) 1 LED (red)<br /> for activity on TER or AUX terminal port (TER) 1 LED (yellow)<br /> for Ethernet link diagnostics (STS) 1 LED (yellow)<br /> for reception activity (RX) 1 LED (yellow)<br /> for transmission activity (TX) 1 LED (yellow)
Current consumption
1680 mA 5 V DC
Module format
Double
Net Weight
1.34 lb(US) (0.61 kg)
Standards
CSA C22.2 No 142<br />CSA C22.2 No 213 Class I Division 2 Group D<br />CSA C22.2 No 213 Class I Division 2 Group B<br />73/23/EEC<br />93/68/EEC<br />89/336/EEC<br />CSA C22.2 No 213 Class I Division 2 Group C<br />IEC 61131-2<br />UL 508<br />92/31/EEC<br />CSA C22.2 No 213 Class I Division 2 Group A
Product Certifications
BV<br />DNV<br />RMRS<br />GL<br />ABS<br />RINA<br />LR
Ambient Air Temperature for Operation
32…140 °F (0…60 °C)
Ambient Air Temperature for Storage
-13…158 °F (-25…70 °C)
Relative Humidity
10…95 % without condensation for operation<br />5…95 % without condensation for storage
Operating altitude
0...6561.68 ft (0...2000 m)
Protective treatment
TC
IP Degree of Protection
IP20
Pollution degree
2

Specifications may be subject to change without notice