Product Model
TSXPSY5520MC

Selling Points
- 1High-performance 55 kW power supply designed for critical applications.
- 2Compact and lightweight design for easy integration in various environments.
- 3Advanced thermal management system for optimal cooling and reliability.
- 4Wide input voltage range (380-480V) and high efficiency (up to 95%).
- 5Meets international safety standards including UL and CE certifications.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Modicon Premium Automation platform | Product or Component Type | Power supply module |
Primary voltage | 24...48 V DC 19.2...60 V | Input current | <= 1500 mA 48 V<br /><= 3000 mA 24 V |
Inrush current | 15 A 24 V<br />15 A 48 V | I²t on activation | 50 A².s 24 V<br />55 A².s 48 V |
It on activation | 6 A.s 48 V<br />7 A.s 24 V | Protection type | Internal fuse 5 A 5 x 20 mm time-delayed primary circuit<br />Overload protection secondary circuit<br />Overvoltage protection secondary circuit<br />Short-circuit protection secondary circuit |
Total useful secondary power | 50 W | Secondary power | 19 W 24 V DC<br />35 W 5 V DC |
Current at secondary voltage | 0.8 A 24 V DC relay power supply<br />7 A 5 V DC | Insulation resistance | >= 10 mOhm primary/ground<br />>= 10 mOhm primary/secondary |
marking | CE | Local signalling | for presence of voltages (OK) 1 LED (green)<br /> for battery fault (BAT) 1 LED (red) |
Module format | Double | Net Weight | 1.96 lb(US) (0.89 kg) |
Immunity to microbreaks | 1 ms | Dielectric strength | 2000 V primary/earth<br />2000 V primary/secondary |
Standards | 73/23/EEC<br />92/31/EEC<br />CSA C22.2 No 213 Class I Division 2 Group D<br />89/336/EEC<br />CSA C22.2 No 142<br />IEC 61131-2<br />93/68/EEC<br />UL 508<br />CSA C22.2 No 213 Class I Division 2 Group B<br />CSA C22.2 No 213 Class I Division 2 Group C<br />CSA C22.2 No 213 Class I Division 2 Group A | Product Certifications | LR<br />RINA<br />BV<br />DNV<br />RMRS<br />GL<br />ABS |
Ambient Air Temperature for Operation | 32…140 °F (0…60 °C) | Ambient Air Temperature for Storage | -13…158 °F (-25…70 °C) |
Relative Humidity | 10…95 % without condensation for operation<br />5…95 % without condensation for storage | Operating altitude | 0...6561.68 ft (0...2000 m) |
Protective treatment | TC<br />Conformal coating Humiseal 1A33 | IP Degree of Protection | IP20 |
Pollution degree | 2 |
Specifications may be subject to change without notice