Product Model
XB4BD25

Selling Points
- 1Compact design for easy installation in tight spaces.
- 2High current capacity for efficient power distribution.
- 3Advanced thermal management for extended lifespan.
- 4Meets international safety standards for secure operation.
- 5Durable construction with high-quality materials for long-term reliability.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Harmony XB4 | Product or Component Type | Selector switch |
Device short name | XB4 | Bezel material | Chromium plated metal |
Fixing collar material | Zamak | Mounting diameter | 0.9 in (22.5 mm) |
Sale per indivisible quantity | 1 | Head type | Standard |
Shape of signaling unit head | Round | Type of operator | stay put |
Operator profile | Black standard handle | Operator position information | 2 positions 90° |
Contacts type and composition | 1 NO + 1 NC | Contact operation | Slow-break |
Connections - terminals | Screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1<br />Screw clamp terminals, >= 1 x 0.22 mm² without cable end IEC 60947-1 | Height | 1.9 in (47 mm) |
Width | 1.2 in (30 mm) | Depth | 2.7 in (68 mm) |
Terminals description ISO n°1 | (13-14)NO<br />(21-22)NC | Net Weight | 0.231 lb(US) (0.105 kg) |
Resistance to high pressure washer | 1015.3 psi (7000000 Pa) 131 °F (55 °C) 0.1 m | Contacts usage | Standard contacts |
Positive opening | With IEC 60947-5-1 appendix K | Torque value | 1.24 lbf.in (0.14 N.m) NO changing electrical state |
Mechanical durability | 1000000 cycles | Tightening torque | 7.08…10.6 lbf.in (0.8…1.2 N.m) IEC 60947-1 |
Shape of screw head | Cross Philips no 1<br />Cross pozidriv No 1<br />Slotted flat Ø 4 mm<br />Slotted flat Ø 5.5 mm | Contacts material | Silver alloy (Ag/Ni) |
Short-circuit protection | 10 A cartridge fuse gG IEC 60947-5-1 | [Ith] conventional free air thermal current | 10 A IEC 60947-5-1 |
[Ui] rated insulation voltage | 600 V 3)IEC 60947-1 | [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-1 |
[Ie] rated operational current | 3 A 240 V, AC-15, A600 IEC 60947-5-1<br />6 A 120 V, AC-15, A600 IEC 60947-5-1<br />0.1 A 600 V, DC-13, Q600 IEC 60947-5-1<br />0.27 A 250 V, DC-13, Q600 IEC 60947-5-1<br />0.55 A 125 V, DC-13, Q600 IEC 60947-5-1<br />1.2 A 600 V, AC-15, A600 IEC 60947-5-1 | Electrical durability | 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C<br />1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C<br />1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN 60947-5-1 appendix C |
Electrical reliability | Λ < 10exp(-6) 5 V 1 mA in clean environment IEC 60947-5-4<br />Λ < 10exp(-8) 17 V 5 mA in clean environment IEC 60947-5-4 | Device presentation | Complete product |
Protective treatment | TH | Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) |
Ambient Air Temperature for Operation | -40…158 °F (-40…70 °C) | Overvoltage category | Class I IEC 60536 |
IP degree of protection | IP69<br />IP69K<br />IP67 IEC 60529 | NEMA degree of protection | NEMA 13<br />NEMA 4X |
Standards | IEC 60947-5-5<br />JIS C8201-5-1<br />UL 508<br />IEC 60947-5-4<br />IEC 60947-1<br />CSA C22.2 No 14<br />IEC 60947-5-1<br />JIS C8201-1 | Product Certifications | BV<br />UL<br />CSA<br />DNV<br />LROS (Lloyds register of shipping) |
Vibration resistance | 5 gn 2…500 Hz)IEC 60068-2-6 | Shock resistance | 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 |
Specifications may be subject to change without notice