schneider ZB4BW0G11

Selling Points

  • 1Universal LED Compatibility: Works with all colors and is easily integrated into existing systems.
  • 2IP66 Rating: Impact, dust, water, and vibration resistant for durable performance.
  • 3Wide Temperature Range: Operates from -40°C to 55°C, ensuring versatility in various environments.
  • 4Easy Installation: Quick and simple assembly and disassembly via screw-clamp connections.
  • 5Standard Compatibility: Fits standard 22mm control and signaling units, ensuring seamless integration into pre-existing machinery.
Product Details
ZB4BW0G11
schneider

Technical Specifications

Detailed engineering parameters based on manufacturer documentation

ParameterValueParameterValue
Range of Product
Harmony XB4
Product or Component Type
Complete body/contact assembly and light block
Device short name
ZB4
Fixing collar material
Zamak
Sale per indivisible quantity
1
Head type
Standard
Contacts type and composition
1 NO
Contact operation
Slow-break
Connections - terminals
Screw clamp terminals, <= 2 x 1.5 mm² with cable end IEC 60947-1<br />Screw clamp terminals, >= 1 x 0.22 mm² without cable end IEC 60947-1
Light source
Universal LED
Bulb base
Integral LED
Light block supply
Direct
Light source colour
White
[Us] rated supply voltage
110...120 V AC 50/60 Hz
CAD overall width
1.2 in (30 mm)
CAD overall height
1.9 in (47 mm)
Terminals description ISO n°1
(13-14)NO
Net Weight
0.141 lb(US) (0.064 kg)
Contacts usage
Standard
Positive opening
Without
Operating travel
0.1 in (2.6 mm) NO changing electrical state)<br />0.2 in (4.3 mm) total travel)
Operating force
2.3 N NO changing electrical state
Operating torque
0.44 lbf.in (0.05 N.m) NO changing electrical state
Mechanical durability
5000000 cycles
Tightening torque
7.08…10.6 lbf.in (0.8…1.2 N.m) IEC 60947-1
Shape of screw head
Cross Philips no 1<br />Cross pozidriv No 1<br />Slotted flat Ø 4 mm<br />Slotted flat Ø 5.5 mm
Contacts material
Silver alloy (Ag/Ni)
Short-circuit protection
10 A cartridge fuse gG IEC 60947-5-1
[Ith] conventional free air thermal current
10 A IEC 60947-5-1
[Ui] rated insulation voltage
600 V 3)IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV IEC 60947-1
[Ie] rated operational current
3 A 240 V, AC-15, A600 IEC 60947-5-1<br />6 A 120 V, AC-15, A600 IEC 60947-5-1<br />0.1 A 600 V, DC-13, Q600 IEC 60947-5-1<br />0.27 A 250 V, DC-13, Q600 IEC 60947-5-1<br />0.55 A 125 V, DC-13, Q600 IEC 60947-5-1<br />1.2 A 600 V, AC-15, A600 IEC 60947-5-1
Electrical durability
1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 IEC 60947-5-1 appendix C
Electrical reliability
Λ < 10exp(-6) 5 V 1 mA in clean environment IEC 60947-5-4<br />Λ < 10exp(-8) 17 V 5 mA in clean environment IEC 60947-5-4
Signalling type
Steady
current consumption
14 mA
Service life
100000 h at rated voltage and 25 °C
Surge withstand
1 kV IEC 61000-4-5
Device presentation
Basic sub-assemblies
Protective treatment
TH
Ambient Air Temperature for Storage
-40…158 °F (-40…70 °C)
Ambient Air Temperature for Operation
-40…158 °F (-40…70 °C)
Electrical shock protection class
Class I IEC 60536
Standards
IEC 60947-5-5<br />IEC 60947-1<br />CSA C22.2 No 14<br />UL 508<br />IEC 60947-5-1<br />IEC 60947-5-4<br />JIS C8201-5-1<br />JIS C8201-1
Product Certifications
DNV<br />UL Listed<br />LROS (Lloyds register of shipping)<br />BV<br />CSA
Vibration resistance
5 gn 2…500 Hz)IEC 60068-2-6
Shock resistance
30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Resistance to fast transients
2 kV IEC 61000-4-4
Resistance to electromagnetic fields
9.1 V/m (10 V/m) IEC 61000-4-3
Resistance to electrostatic discharge
6 kV on contact (on metal parts) IEC 61000-2-6<br />8 kV in free air (in insulating parts) IEC 61000-2-6
Electromagnetic emission
Class B IEC 55011

Specifications may be subject to change without notice