Product Model
ZB4BW0G524

Selling Points
- 1IP66 rated for impact, dust, water, and vibration resistance.
- 2Fast and simple replacement with clip-together assembly and screw-clamp connections.
- 3Integral LED for clear visual distinction of signaling units.
- 4Compatible with Harmony XB4 pilot lights and standard 22mm control units.
- 5Operating temperatures from -40°C to 55°C ensure versatile usage in various environments.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Harmony XB4 | Product or Component Type | Complete body/contact assembly and light block |
Device short name | ZB4 | Fixing collar material | Zamak |
Sale per indivisible quantity | 1 | Contacts type and composition | 1 NC |
Contact operation | Slow-break | Connections - terminals | Plug-in connector |
Light source | Protected LED | Bulb base | Integral LED |
Light block supply | Direct | Light source colour | Orange |
[Us] rated supply voltage | 110...120 V AC 50/60 Hz | CAD overall width | 1.2 in (30 mm) |
CAD overall height | 1.9 in (47 mm) | Terminals description ISO n°1 | (11-12)NC |
Contacts usage | Standard | Positive opening | With EN/IEC 60947-5-1 appendix K |
Operating travel | 0.06 in (1.5 mm) NC changing electrical state)<br />0.2 in (4.3 mm) total travel) | Operating force | 2 N NC changing electrical state |
Mechanical durability | 5000000 cycles | Contacts material | Silver alloy (Ag/Ni) |
Short-circuit protection | 4 A cartridge fuse gG EN/IEC 60947-5-1 | [Ith] conventional free air thermal current | 10 A EN/IEC 60947-5-1 |
[Ui] rated insulation voltage | 250 V 3)EN/IEC 60947-1 | [Uimp] rated impulse withstand voltage | 4 kV EN 60947-1 |
[Ie] rated operational current | 3 A 240 V, AC-15, A300 EN/IEC 60947-5-1<br />6 A 120 V, AC-15, A300 EN/IEC 60947-5-1<br />0.1 A 250 V, DC-13, R300 EN/IEC 60947-5-1<br />0.22 A 125 V, DC-13, R300 EN/IEC 60947-5-1 | Electrical durability | 1000000 cycles, AC-15, 1 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 1.5 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, AC-15, 3 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.15 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C<br />1000000 cycles, DC-13, 0.4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C |
Electrical reliability | Λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4<br />Λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4 | Signalling type | Steady |
current consumption | 14 mA | Service life | 100000 h at rated voltage and 25 °C |
Surge withstand | 1 kV IEC 61000-4-5 | Protective treatment | TH |
Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) | Ambient Air Temperature for Operation | -40…158 °F (-40…70 °C) |
Electrical shock protection class | Class I IEC 60536 | Standards | EN/IEC 60947-5-5<br />EN/IEC 60947-5-1<br />JIS C8201-5-1<br />CSA C22.2 No 14<br />EN/IEC 60947-1<br />UL 508<br />EN/IEC 60947-5-4<br />JIS C8201-1 |
Product Certifications | LROS (Lloyds register of shipping)<br />BV<br />CSA<br />DNV<br />UL Listed<br />GL | Vibration resistance | 5 gn 2…500 Hz)IEC 60068-2-6 |
Shock resistance | 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27<br />50 gn 11 ms) half sine wave acceleration IEC 60068-2-27 | Resistance to fast transients | 2 kV IEC 61000-4-4 |
Resistance to electromagnetic fields | 9.1 V/m (10 V/m) IEC 61000-4-3 | Resistance to electrostatic discharge | 6 kV on contact (on metal parts) IEC 61000-2-6<br />8 kV in free air (in insulating parts) IEC 61000-2-6 |
Electromagnetic emission | Class B IEC 55011 |
Specifications may be subject to change without notice