Product Model
ZBRN2

Selling Points
- 1Wireless Connectivity: The ZBRN2 offers reliable wireless connectivity, ensuring smooth data transfer between devices.
- 2Modbus Compatibility: Compatible with Modbus serial line communication, making it suitable for various industrial automation systems.
- 3Versatile Range: Supports a range of up to 100 meters in free field conditions, with options to extend the range using relay or external antennas.
- 4Durable Design: Built with a robust design, suitable for harsh industrial environments and DIN rail mounting.
- 5Easy Installation: Simple installation process with clear instructions, ensuring quick setup and minimal downtime.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Range of Product | Harmony | Product or Component Type | Harmony Hub wireless/Serial Line gateway |
Device short name | ZBRN2 | Product Specific Application | Wireless Schneider Electric devices ecosystem |
Function of module | Zigbee green power concentrator | Communication port protocol | Modbus client application |
Antenna type | Integrated | Transmission frequency | 2405…2480 MHz |
Maximum radio communication distance | 328.08 ft (100 m) in free field<br />820.2 ft (250 m) if a relay antenna is located between the transmitter and Harmony Hub<br />196.9 ft (60 m) if an external antenna is connected to Harmony Hub<br />82.02 ft (25 m) with Harmony Hub installed in a metal housing or in a closed metal enclosure | Radio response time | < 30 ms |
Radio channels utilisation | <= 60 devices | [Us] Rated Supply Voltage | 24...240 V AC/DC 50/60 Hz - 10...10 % |
Immunity to microbreaks | 10 ms | Maximum power consumption in W | 4 W AC/DC |
Breaking capacity | 750 VA | Control circuit frequency | 50...60 Hz +/- 10 % |
Short-circuit protection | 16 A GB2 circuit breaker | Operating position | Any position |
Mounting support | 35 mm symmetrical DIN rail conforming to EN/IEC 60715<br />Mounting plate | Electrical connection | 1 conductor cable 0.0003…0.006 in² (0.2…4 mm²) - AWG 24...AWG 12 - solid - without cable end IEC 60947-1<br />2 conductors cable 0.0003…0.002 in² (0.2…1.5 mm²) - AWG 24...AWG 16 - solid - without cable end IEC 60947-1<br />1 conductor cable 0.0003…0.001 in² (0.2…0.75 mm²) - AWG 24...AWG 14 - flexible - with cable end IEC 60947-1<br />2 conductors cable 0.0003…0.004 in² (0.2…2.5 mm²) - AWG 24...AWG 18 - flexible - with cable end IEC 60947-1 |
Tightening torque | 3.10…3.5 lbf.in (0.35…0.4 N.m) EN/IEC 60947-1<br />3.09…3.54 lbf.in (0.35…0.40 N.m) EN/IEC 60947-1 | Housing material | Self-extinguishing plastic |
Status LED | 1 LED Green power ON<br />1 LED Yellow communication network<br />5 LEDs Red function mode<br />1 LED green and yellow reception signal | Rated short-duration power frequency withstand voltage | 1.5 kV 50 Hz EN/IEC 60947-5-1 |
[Uimp] rated impulse withstand voltage | 4 kV | Surge withstand | 1 kV differential mode IEC 61000-4-5<br />2 kV common mode IEC 61000-4-5 |
Width | 4.8 in (122 mm) | Height | 3.5 in (90 mm) |
Depth | 2.4 in (60 mm) | Net Weight | 0.60 lb(US) (0.27 kg) |
Antenna gain | 0 dBi | Integrated connection type | 1 isolated serial link 2 x RJ45 in parallel Modbus Serial line slave Modbus slave RTU asynchronous in baseband RS485, half duplex, 1.2...115.2 kbauds, 2 twisted shielded pairs |
Data storage equipment | SD card | Topology | Devices linked by daisy-chaining or tap junctions |
Data format | 7 or 8 bits, 1 or 2 stop bits | Parity | No<br />Even<br />Odd |
Radio agreement | ANATEL, type III ETSI EN 301 489-3<br />FCC, category 2 ETSI EN 300 440-1<br />ICASA<br />RSS, category 1 ETSI EN 300 440-1<br />SRRC | Product Certifications | GOST<br />CE<br />UL<br />C-tick<br />CSA<br />CCC |
Directives | 2006/95/EC - low voltage directive<br />2004/108/EC - electromagnetic compatibility<br />1999/5/EC - R&TTE directive | Standards | CSA C22.2 No 14<br />EN 62311<br />EN/IEC 61131-2<br />ETSI EN 300 440-2<br />ETSI EN 300 328<br />EN/IEC 60950-1<br />UL 508 |
Ambient Air Temperature for Storage | -40…158 °F (-40…70 °C) | Relative humidity | 90 % -13…131 °F (-25…55 °C), without condensation ETSI EN 300 440-1 |
Operating altitude | 0...6561.68 ft (0...2000 m) | Storage altitude | 0.0000000000…9842.5 ft (0…3000 m) |
Vibration resistance | +/- 3.5 mm 5…14 Hz) IEC 60068-2-6<br />1 gn 5…150 Hz) on panel mounting IEC 60068-2-6<br />2 gn 8…150 Hz) on DIN rail IEC 60068-2-6 | Shock resistance | 10 gn 16 ms) 6000 shocks IEC 60068-2-27 |
IP degree of protection | IP20 IEC 60529 casing)<br />IP20 terminals) | Pollution degree | 2 IEC 60664-1 |
Electromagnetic compatibility | 1.2/50 µs shock waves immunity test - test level: 1 kV (differential mode) conforming to IEC 61000-4-5<br />1.2/50 µs shock waves immunity test - test level: 2 kV (common mode) conforming to IEC 61000-4-5<br />Immunity to microbreaks and voltage drops - test level: 10 ms conforming to IEC 61000-4-11 | Dielectric strength | 3000 V between input and output AC<br />4250 V between input and output DC<br />1500 V between input and ground AC<br />2150 V between input and ground DC |
Specifications may be subject to change without notice