Product Model
IM30-15NUS-ZUX

Selling Points
- 1High Detection Range: Detects objects up to 15mm with assured sensing range of 12.15mm.
- 2Robust Design: Features a cylindrical housing with M30 x 1.5 thread size and IP67 enclosure rating.
- 3Versatile Power Supply: Operates on 20V AC/DC to 250V AC/DC with a voltage drop ≤6.5V AC and ≤6V DC.
- 4Fast Response Time: Offers a time delay before availability ≤8ms and hysteresis 1% to 15%.
- 5Durable Construction: Built with nickel-plated brass housing and PVC cable material for high resistance to shock and vibrations.
Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Housing | Metric | Housing | Standard design |
Thread size | M30 x 1.5 | Diameter | Ø 30 mm |
Sensing range Sn | 15 mm | Installation type | Non-flush |
Switching frequency | 25 Hz1)#!#30 Hz2) | Connection type | Cable, 2-wire, 2 m |
Output function | NO | Electrical wiring | AC/DC 2-wire |
Enclosure rating | IP67 | Special characteristic | Series connectable |
Items supplied | Mounting nut, brass, nickel-plated (2x) | Supply voltage | 20 V AC/DC ... 250 V AC/DC |
Voltage drop | ≤ 6.5 V | Time delay before availability | ≤ 8 ms |
Hysteresis | 1 % ... 15 % | Reproducibility | ≤ 10 % |
Temperature drift (of Sr) | ± 10 % | EMC | According to EN 60947-5-2#!#As per EN 55011, class B |
Continuous current Ia | ≤ 200 mA | Off-state current | ≤ 4 mA |
Minimum load current | ≥ 5 mA | Short-time withstand current | 2.2 A |
Cable material | PVC | Conductor size | 0.5 mm² |
Short-circuit protection | — | Power-up pulse protection | ✔ |
Shock and vibration resistance | 30 g, 11 ms / 10 ... 55 Hz, 1 mm | Ambient operating temperature | –25 °C ... +70 °C |
Housing material | Brass, nickel-plated | Sensing face material | Plastic, PBT |
Housing length | 81 mm | Thread length | 44 mm |
Tightening torque, max. | ≤ 50 Nm | Protection class | II |
Rated insulation voltage Ui | 250 V AC | Usage category | AC-1406)#!#DC-137) |
Contamination rating | 3 | Rated impulse withstand voltage | 4 kV |
Remark | Associated graphic see "Installation" |
Specifications may be subject to change without notice