Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Housing | Metric | Housing | Standard design |
Thread size | M30 x 1.5 | Diameter | Ø 30 mm |
Sensing range Sn | 20 mm | Safe sensing range Sa | 16.2 mm |
Installation type | Non-flush | Switching frequency | 500 Hz |
Connection type | Male connector M12, 4-pin | Switching output | PNP |
Output function | NO | Electrical wiring | DC 3-wire |
Enclosure rating | IP67 | Special features | Resistant against coolant lubricants, Visual adjustment indicator, IO-Link, Temperature resistance |
Special applications | Zones with coolants and lubricants, Mobile machines, Difficult application conditions, Explosive areas | Items supplied | Mounting nut, V2A stainless steel, with locking teeth (2x)#!#Cable housing/cover |
Supply voltage | 10 V DC ... 30 V DC | Ripple | ≤ 10 % |
Voltage drop | ≤ 2 V | Hysteresis | 3 % ... 20 % |
Reproducibility | ≤ 2 % | Temperature drift (of Sr) | ± 10 % |
EMC | According to EN 60947-5-2 | Continuous current Ia | ≤ 200 mA |
No load current | ≤ 10 mA | Short-circuit protection | ✔ |
Power-up pulse protection | ✔ | Shock and vibration resistance | 100 g / 2 ms / 500 cycles; 150 g / 1 Mio cycles; 10 Hz ... 55 Hz / 1 mm; 55 Hz ... 500 Hz / 60 g |
Ambient operating temperature | –20 °C ... +95 °C | Housing material | Stainless steel V2A, DIN 1.4305 / AISI 303 |
Sensing face material | Plastic, LCP | Housing length | 70 mm |
Thread length | 40 mm | Tightening torque, max. | Typ. 100 Nm5)#!#Typ. 100 Nm6) |
ATEX marking | II 3G Ex ec IIC T4 Gc X, II 3D Ex tc IIIC T135°C Dc X | Ex area category | 3G, 3D |
Protection class | III | UL File No. | E181493 |
Communication interface | IO-Link V1.0 | Communication Interface detail | COM2 (38,4 kBaud) |
Process data length | 1 Byte | Process data structure | Bit 0 = Sr reached#!#Bit 1 = Sa reached |
Note | The values are reference values which may vary | St37 steel (Fe) | 1 |
Stainless steel (V2A, 304) | Approx. 0.78 | Aluminum (Al) | Approx. 0.44 |
Copper (Cu) | Approx. 0.36 | Brass (Br) | Approx. 0.46 |
Remark | Associated graphic see "Installation" | A | 20 mm |
B | 62 mm | C | 30 mm |
D | 60 mm | E | 20 mm |
F | 160 mm |