Technical Specifications
Detailed engineering parameters based on manufacturer documentation
Parameter | Value | Parameter | Value |
---|---|---|---|
Housing | Rectangular | Dimensions (W x H x D) | 12 mm x 40 mm x 26 mm |
Sensing range Sn | 0 mm ... 4 mm | Safe sensing range Sa | 3.24 mm |
Number of switching points | Up to 4 adjustable switching points or windows | Switching modes | Single point, Window mode, Two point mode, Visual adjustment indicator |
Switching frequency Qint.1 / Qint.2 on Pin2 | 1,000 Hz | Installation type | Flush |
Connection type | Cable with M12 male connector, 4-pin, 0.2 m | Switching output | PNP |
Output Q/C | Switching output or IO-Link mode | Output MFC | Switching output or input |
Output function | NC / NO | Output characteristic | Programmable |
Electrical wiring | DC 4-wire | Enclosure rating | IP68 |
Special features | Smart Task, IO-Link | Pin 2 configuration | External input, Teach-in, switching signal |
Supply voltage | 10 V DC ... 30 V DC | Ripple | ≤ 10 % |
Voltage drop | ≤ 2 V | Hysteresis | Programmable |
Reproducibility | ≤ 5 %4)#!#5) | Temperature drift (of Sr) | ± 10 % |
EMC | According to EN 60947-5-2 | Continuous current Ia | ≤ 200 mA |
No load current | 35 mA | Short-circuit protection | ✔ |
Power-up pulse protection | ✔ | Shock and vibration resistance | 30 g, 11 ms / 10 ... 55 Hz, 1 mm |
Ambient operating temperature | –25 °C ... +75 °C | Housing material | Plastic, VISTAL® |
Sensing face material | Plastic, VISTAL® | Tightening torque, max. | < 1 Nm |
Teach-in accuracy | +/- 3% of Sr | Resolution, typical (range) | 20 μm (0 mm ... 4 mm) |
Resolution, maximum (area) | 40 μm (0 mm ... 4 mm) | Communication interface | IO-Link V1.1 |
Communication Interface detail | COM2 (38,4 kBaud) | Cycle time | 5 ms |
Process data length | 32 Bit | Process data structure | Bit 0 = switching signal QL1#!#Bit 1 = switching signal QL2#!#Bit 2 = switching signal QInt3#!#Bit 3 = switching signal QInt4#!#Bit 18 ... 31 = time value |
Factory setting | Switching Point 1: reference value 1#!#Output: normally open#!#Pin 2 configuration: input | Note | Reference value in Digits for switching point in mm stored in the sensor |
Reference value 1 | 4 mm | Reference value 2 | 3 mm |
Reference value 3 | 2 mm | Reference value 4 | 1 mm |
Stainless steel (V2A, 304) | Approx. 0.7 | Aluminum (Al) | Approx. 0.4 |
Copper (Cu) | Approx. 0.3 | Brass (Br) | Approx. 0.4 |
Remark | Associated graphic see "Installation" | A | 0 mm |
B | 12 mm | C | 12 mm |
D | 12 mm | E | 0 mm |
F | 32 mm | G | 0 mm |
Smart Task name | Time measurement + debouncing | Logic function | Window#!#Direct |
Timer function | Deactivated#!#Switch-on delay#!#Off delay#!#ON and OFF delay#!#Impulse (one shot) | Inverter | Adjustable |
Time measurement accuracy | SIO Logic: (-1,2 ... 0) x time base ± 1 % of time measurement value1)#!#IOL: (-1,2 ... 0) x time base ± 1 % of time measurement value2) | Time measurement accuracy (e.g. accuracy for time measurement value = 1 s ) | Time base 1 ms: –11,2 ms ... 10 ms |
Resolution time measuring value | 1 ms | Debounce time max. | SIO Logic: 30 s1)#!#IOL: 30 s2) |
Switching signal_Switching signal QL1 | Output type (dependant on the adjusted threshold) | Switching signal_Switching signal QL2 | Output type (dependant on the adjusted threshold) |
Measuring value | Time measurement value |